Plan Review Notes
Plan Review Notes For Permit 19120280
Permit Number 19120280
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-12 15:50:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS OF SITE ACCESS THRU THE
 FENCE.
  
 IF THIS IS FOR A CONSTRUCTION PROJECT, FD REQUIRES SITE
 ACCESS IN THE EVENT OF EMERGENCY.
  
 THE MINIMUM WIDTH IS 20'; TWO 10' GATES.
  
 18.2.1 FIRE DEPARTMENT ACCESS AND FIRE DEPARTMENT
 ACCESS ROADS SHALL
 BE PROVIDED AND MAINTAINED IN ACCORDANCE WITH SECTION
 18.2.
  
 18.2.3.1 REQUIRED ACCESS.
 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL
 BE PROVIDED
 FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING
 HEREAFTER
 CONSTRUCTED OR RELOCATED.
 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST
 OF ROADWAYS, FIRE
 LANES, PARKING LOT LANES, OR A COMBINATION THEREOF.
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE REVIEW AND PROVIDE THE SIZE AND LOCATION OF THE
 GATE.
  
 A KNOX PADLOCK IS RECOMMENDED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  