Plan Review Notes For Permit 19120280 |
Permit Number |
19120280 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-12 15:50:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1) THERE ARE NO INDICATIONS OF SITE ACCESS THRU THE | | FENCE. | | | | IF THIS IS FOR A CONSTRUCTION PROJECT, FD REQUIRES SITE | | ACCESS IN THE EVENT OF EMERGENCY. | | | | THE MINIMUM WIDTH IS 20'; TWO 10' GATES. | | | | 18.2.1 FIRE DEPARTMENT ACCESS AND FIRE DEPARTMENT | | ACCESS ROADS SHALL | | BE PROVIDED AND MAINTAINED IN ACCORDANCE WITH SECTION | | 18.2. | | | | 18.2.3.1 REQUIRED ACCESS. | | 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL | | BE PROVIDED | | FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING | | HEREAFTER | | CONSTRUCTED OR RELOCATED. | | 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST | | OF ROADWAYS, FIRE | | LANES, PARKING LOT LANES, OR A COMBINATION THEREOF. | | | | 18.2.3.4.1 DIMENSIONS. | | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | UNOBSTRUCTED | | WIDTH OF NOT LESS THAN 20 FT (6.1 M). | | | | PLEASE REVIEW AND PROVIDE THE SIZE AND LOCATION OF THE | | GATE. | | | | A KNOX PADLOCK IS RECOMMENDED. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|