2019-12-14 07:19:26 | PLAN REVIEW - BUILDING |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. SITE PLAN PAGE SP-1.01 INDICATES THE 4 FOOT HIGH |
| WALL LOCATED AT THE FRONT ELEVATION OF THE PROPERTY |
| ENCROACHS INTO THE 6 FOOT FPL EASEMENT. PROVIDE |
| EASEMENT RELEASE FROM FPL. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. REF. PLAN PAGE S-001 - PROVIDE DETAIL FOR 12X12 CMU |
| PIERS. |
| R606.7PIERS. |
| THE UNSUPPORTED HEIGHT OF MASONRY PIERS SHALL NOT |
| EXCEED 10 TIMES THEIR LEAST DIMENSION. WHERE STRUCTURAL |
| CLAY TILE OR HOLLOW CONCRETE MASONRY UNITS ARE USED FOR |
| ISOLATED PIERS TO SUPPORT BEAMS AND GIRDERS, THE |
| CELLULAR SPACES SHALL BE FILLED SOLIDLY WITH GROUT OR |
| TYPE M OR S MORTAR, EXCEPT THAT UNFILLED HOLLOW PIERS |
| SHALL BE PERMITTED TO BE USED IF THEIR UNSUPPORTED |
| HEIGHT IS NOT MORE THAN FOUR TIMES THEIR LEAST |
| DIMENSION. WHERE HOLLOW MASONRY UNITS ARE SOLIDLY |
| FILLED WITH GROUT OR TYPE M, S OR N MORTAR, THE |
| ALLOWABLE COMPRESSIVE STRESS SHALL BE PERMITTED TO BE |
| INCREASED AS PROVIDED IN TABLE R606.9. |
| R606.7.1PIER CAP. |
| HOLLOW PIERS SHALL BE CAPPED WITH 4 INCHES (102 MM) OF |
| SOLID MASONRY OR CONCRETE, A MASONRY CAP BLOCK, OR |
| SHALL HAVE CAVITIES OF THE TOP COURSE FILLED WITH |
| CONCRETE OR GROUT. |
| |
| 3. A 2ND SIGNATURE REVIEW WILL BE REQUIRED DUE TO NEW |
| PLAN PAGES. |
| UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, |
| INSERT CORRECTED PAGES INTO |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS |
| DETACHED. |
| |
| |
| |