Plan Review Notes For Permit 19120262 |
Permit Number |
19120262 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-06 16:01:55 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 19120262 | | REVIEWED: DECEMBER 6, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC[B] = FBC BUILDING | | FBC[EXISTING] = FBC EXISTING BUILDING | | | | THE SYSTEM SELECTED(W-20) IS RATED FOR -52.5. THE THAT | | PRESSURE WILL MEET ZONE 1 AND 2, BUT FALLS SHORT OF | | ZONE 3 (CORNERS) | | PLEASE PROVIDE ENGINEERING TO SHOW ENHANCED NAILING, OR | | SELECT SYSTEM WITH HIGHER PRESSURE RATING. W-21 WOULD | | WORK. | | | | EITHER PROVIDE 2 COPIES ENGINEERING, OR COME IN AND | | CHANGE THE SYSTEM SELECTION. | | THE PERMIT WILL BE ISSUED AT THAT TIME. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | |
|