Plan Review Notes
Plan Review Notes For Permit 19120167
Permit Number 19120167
Review Stop G
Sequence Number 1
Notes
Date Text
2020-01-07 10:26:051) THE EXISTING PLANS ON FILE WITH THE CITY SHOW THIS
 SYSTEM AS A NATURAL GAS SYSTEM.ALL APPLIANCES AND
 EQUIPMENT SHALL NOT BE USED FOR LP GAS UNLESS IT IS
 CONVERTED TO USE LP GAS AND IS TESTED FOR PERFORMANCE
 WITH LP GAS BEFORE BEING PLACED INTO USE.PER NFPA 58
 SEC.5.20.2.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1. ALL
 REGULATORS FOR OUTDOOR INSTALLATIONS SHALL BE DESIGNED,
 INSTALLED, OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS PER NFPA 58 SEC.6.8.1.4. THE
 REGULATORS SHALL BE LISTED FOR EXTERIOR USE.
 3) SUBMIT DOCUMENTATION FOR COMPLIANCE WITH THE
 REQUIREMENTS OF 2017 FBC-FUEL GAS CODE SEC.301.10 FOR
 WIND RESISTANCE. A SHEET HAS BEEN SUBMITTED SHOWING
 EYEBOLTS, METAL CABLE AND CLAMPS. ADDITIONAL
 DOCUMENTATION IS REQUIRED TO SHOW COMPLIANCE WITH 2017
 FBC-BUILDING SEC.1609.1 FOR WIND LOAD.
 4) COPPER TUBING SHALL BE EITHER TYPE K OR L PER NFPA
 58 SEC.5.9.3.2 (2).
 5) INDICATE ON THE PLANS THE TYPE OF FOUNDATION THAT
 THE TANKS ARE RESTING UPON.
 6) INDICATE ON THE PLANS IF THE TANKS WILL BE EXCHANGED
 OR IF THEY WILL BE FILLED ONSITE.IF FILLED ONSITE, THE
 OPERATIONS SHALL COMPLY WITH CHAPTER 7 OF NFPA 58.
 7) INDICATE ON THE PLANS THE HEIGHT OF THE BOLLARDS
 ABOVE GROUND, THE EMBEDMENT DEPTH BELOW GROUND AND THE
 TYPE OF MATERIAL FROM WHICH THEY ARE CONSTRUCTED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 8) THE EXISTING GAS PLANS ON FILE WITH THE CITY SHOW A
 TOTAL BTU LOAD OF 1,020,000 BUT THE PLAN SUBMITTED FOR
 THIS PROJECT NOTE A BTU LOAD OF 500,000 BTU'S. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  