Plan Review Notes
Plan Review Notes For Permit 19120065
Permit Number 19120065
Review Stop G
Sequence Number 1
Notes
Date Text
2019-12-27 07:39:40GAS 1ST REVIEW**DENIED**19120065
 1) PROVIDE DRIP LEG WITH IN 10 PIPE DIAMETERS OF THE
 GAS REGULATOR. FBC-GAS 410.2
 2) PROVIDE GENERATOR INSTALLATION MANUAL OR APPROVE
 PERMIT # FOR GENERATOR. FBC 107.3.5
 3) THE TANK TIE DOWN SHEETS ARE SIGN BY AN ARCHITECT
 WERE ITS CALLING FOR AN ENGINEER. SHOW WERE AN
 ARCHITECT HAS THE AUTHORITY TO APPROVED THESE DRAWING
 WITH IN HIS SCOPE OF LICENSE. FBC 107.2.1
 4) THE SIGN AND SEAL BY THE ARCHITECT IS A COPY. PLAN
 MUST BE DIGITALLY SIGNED AND SEAL PER FAC 61G1-16.005.
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE 1ST AND
 2ND STAGE PRESSURE REGULATORS. REGULATORS INSTALLED ON
 THE EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR
 OUTDOOR INSTALLATION. 2017 FGC SEC.410.1
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  