Plan Review Notes
Plan Review Notes For Permit 19120033
Permit Number 19120033
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-17 16:00:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3 PROVIDE THE
 FOLLOWING INFORMATION
 DRAWING INDEX NOTES PLUMBING DRAWINGS PLAN SHEETS P-1
 AND P-2. PROVIDE THESE DRAWINGS FOR COMPREHENSIVE
 REVIEW.
 BASED UPON THE THE SCOPE OF WORK NOTES AND THE
 RECONFIGURATIONS NOTED BELOW, THE CLASSIFICATION OF
 WORK IS LEVEL 2, NOT LEVEL 1.
 ADDITIONAL COMMENTS AFTER REVIEW OF PLAN SHEETS A-1 AND
 D-1
 1. PLAN SHEET D-1 (DRAWING INDEX NOTES A-2 AS
 DEMOLITION PLAN; PLEASE CLARIFY): DEMOLITION PLAN.
 EXISTING WATER HEATERS; SHOW LOCATION OF EXISTING WATER
 HEATERS IN END APARTMENTS. PROVIDE EXISTING WATER
 HEATER SCHEDULE INDICATING STORAGE CAPACITY AND
 ELECTRICAL CHARACTERISTICS.
 2. PLAN SHEET A-1; SHOW LOCATION OF ALL WATER HEATERS
 ON FINISH FLOOR PLAN. KITCHENS ARE RECONFIGURED.
 3. PLAN SHEET A-1; SCOPE OF WORK. KITCHENS ARE
 RECONFIGURED. EXISTING WATER HEATERS SHALL BE REPLACED
 WITH NEW WATER HEATERS. PROVIDE DETAIL AND WATER HEATER
 SCHEDULE INDICATING MANUFACTURER, MODEL, STORAGE
 CAPACITY AND ELECTRICAL CHARACTERISTICS. COMPLY WITH
 FBC PL SECTION 504 AND FBC PL 607.3.
 4. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A
 SANITARY RISER DIAGRAM AND PLAN VIEW LAYOUT TO SHOW
 CHANGES. COMPLY WITH FBC PL CHAPTER 7 AND CHAPTER 9
 5. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A
 WATER DISTRIBUTION RISER DIAGRAM AND PLAN VIEW LAYOUT
 TO SHOW CHANGES. COMPLY WITH FBC PL CHAPTER 6.
 6. PROVIDE SHOWER DETAIL (ELEVATION VIEW). SHOW
 COMPLIANCE WITH FBC PL SECTION 417.
 7. PROVIDE MATERIAL TYPE FOR SANITARY DRAINS AND VENTS.
 8. PROVIDE MATERIAL TYPE FOR WATER DISTRIBUTION
 9. PROVIDE UL RATED ASSEMBLIES FOR THROUGH THE FLOOR
 PIPING PENETRATIONS IN THE ELEVATED FLOOR. COMPLY WITH
 FBC CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19120033 710 10TH ST
  