Date |
Text |
2019-12-17 16:00:31 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMENTS: DENIED |
| |
| PER WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3 PROVIDE THE |
| FOLLOWING INFORMATION |
| DRAWING INDEX NOTES PLUMBING DRAWINGS PLAN SHEETS P-1 |
| AND P-2. PROVIDE THESE DRAWINGS FOR COMPREHENSIVE |
| REVIEW. |
| BASED UPON THE THE SCOPE OF WORK NOTES AND THE |
| RECONFIGURATIONS NOTED BELOW, THE CLASSIFICATION OF |
| WORK IS LEVEL 2, NOT LEVEL 1. |
| ADDITIONAL COMMENTS AFTER REVIEW OF PLAN SHEETS A-1 AND |
| D-1 |
| 1. PLAN SHEET D-1 (DRAWING INDEX NOTES A-2 AS |
| DEMOLITION PLAN; PLEASE CLARIFY): DEMOLITION PLAN. |
| EXISTING WATER HEATERS; SHOW LOCATION OF EXISTING WATER |
| HEATERS IN END APARTMENTS. PROVIDE EXISTING WATER |
| HEATER SCHEDULE INDICATING STORAGE CAPACITY AND |
| ELECTRICAL CHARACTERISTICS. |
| 2. PLAN SHEET A-1; SHOW LOCATION OF ALL WATER HEATERS |
| ON FINISH FLOOR PLAN. KITCHENS ARE RECONFIGURED. |
| 3. PLAN SHEET A-1; SCOPE OF WORK. KITCHENS ARE |
| RECONFIGURED. EXISTING WATER HEATERS SHALL BE REPLACED |
| WITH NEW WATER HEATERS. PROVIDE DETAIL AND WATER HEATER |
| SCHEDULE INDICATING MANUFACTURER, MODEL, STORAGE |
| CAPACITY AND ELECTRICAL CHARACTERISTICS. COMPLY WITH |
| FBC PL SECTION 504 AND FBC PL 607.3. |
| 4. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A |
| SANITARY RISER DIAGRAM AND PLAN VIEW LAYOUT TO SHOW |
| CHANGES. COMPLY WITH FBC PL CHAPTER 7 AND CHAPTER 9 |
| 5. BATHROOMS ANDS KITCHENS ARE RECONFIGURED. PROVIDE A |
| WATER DISTRIBUTION RISER DIAGRAM AND PLAN VIEW LAYOUT |
| TO SHOW CHANGES. COMPLY WITH FBC PL CHAPTER 6. |
| 6. PROVIDE SHOWER DETAIL (ELEVATION VIEW). SHOW |
| COMPLIANCE WITH FBC PL SECTION 417. |
| 7. PROVIDE MATERIAL TYPE FOR SANITARY DRAINS AND VENTS. |
| 8. PROVIDE MATERIAL TYPE FOR WATER DISTRIBUTION |
| 9. PROVIDE UL RATED ASSEMBLIES FOR THROUGH THE FLOOR |
| PIPING PENETRATIONS IN THE ELEVATED FLOOR. COMPLY WITH |
| FBC CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19120033 710 10TH ST |
| |