Plan Review Notes For Permit 19120033 |
Permit Number |
19120033 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-04 15:02:30 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THERE IS AN INDICATION OF INSTALLING NEW SMOKE | | DETECTORS IN THE BEDROOMS/SLEEPING AREAS. | | | | SMOKE ALARMS ARE TO INSTALLED OUTSIDE SLEEPING AREAS | | PER NFPA 101, CH 31, EXISTING APARTMENT OCCUPANCIES' | | | | 31.3.4.5 SMOKE ALARMS. | | 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED | | THROUGHOUT WITH AN | | EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM, | | SMOKE ALARMS | | SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS | | MODIFIED BY 31.3.4.5.2, | | OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY | | OF THE BEDROOMS | | AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING | | BASEMENTS. | | 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL | | NOT BE REQUIRED TO | | BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE. | | | | PLEASE PROVIDE SMOKE ALARMS IN THE HALL AREAS OF EACH | | UNIT. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|