Plan Review Notes
Plan Review Notes For Permit 19111273
Permit Number 19111273
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-12 09:40:051) PLEASE SUBMIT A NARRATIVE OR EXPLANATION OF THE
 CHANGES THAT HAVE BEEN MADE TO THE PLUMBING OR GAS
 SYSTEMS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE SANITARY RISER DOES NOT COMPLY WITH THE
 REQUIREMENTS OF A CIRCUIT VENT SYSTEM PER 2017
 FBC-PLUMBING SEC/ 914.1, 914.1.1, 914.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW