Date |
Text |
2019-11-30 10:46:26 | PLAN REVIEW - MECHANICAL |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE SERVICE OUTLET AT CONDENSING UNIT PER |
| E3901.12 |
| E3901.12 HVAC OUTLET. |
| |
| 2. SHOW FLEX DUCT TO BATHROOM. SHOW SIZE AND CFM. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 3. RETURN AIR SHALL COMPLY WITH M1602.2. |
| PROVIDE CFM'S AT EACH SUPPLY. BALANCED RETURN AIR SHALL |
| COMPLY WITH 1602.3. 50 SQ. INCHES FOR EACH 100 CFM OF |
| SUPPLY. |
| |
| 4. SHOW LOCATION OF EXHAUST FANS ON PLANS. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. PROVIDE LOCATION OF DRYER EXHAUST ON PLANS. EXHAUST |
| TERMINATION SHALL COMPLY WITH M1502.3. |
| |
| 6. SHOW LOCATION OF ATTIC ACCESS ON PLANS. ACCESS SHALL |
| COMPLY WITH M1305.1.3. SWITCHED LUMINARE AND SERVICE |
| OUTLET ARE REQUIRED FOR MECH. EQUIPT. IN ATTICS. |
| M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, |
| INSERT CORRECTED PAGES INTO |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS |
| DETACHED. |
| |
| |
| |