Plan Review Notes
Plan Review Notes For Permit 19111230
Permit Number 19111230
Review Stop E
Sequence Number 1
Notes
Date Text
2019-12-03 10:39:02PLAN REVIEW - ELECTRICAL
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AIC:
  
 PROVIDE ACTUAL TRANSFORMER SECONDARY FAULT CURRENT FROM
 UTILITY.
 E3404.2INTERRUPTING RATING.
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS
 SHALL HAVE A MINIMUM INTERRUPTING RATING OF 10,000
 AMPERES. EQUIPMENT INTENDED TO INTERRUPT CURRENT AT
 LEVELS OTHER THAN FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL CIRCUIT VOLTAGE OF NOT
 LESS THAN THE CURRENT THAT MUST BE INTERRUPTED. (110.9)
  
 2. PANEL SCHEDULE STATES PANELS A&B. PLEASE CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. CIRCUTS 15 AND 17 FOR SMALL APPLIANCE SHALL BE A
 MINIMUM OF 20 AMP PER E3703.2 & E3902.3.
 E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING.
 E3901.3 SMALL APPLIANCE RECEPTACLES.
 IN THE KITCHEN, PANTRY, BREAKFAST ROOM, DINING ROOM, OR
 SIMILAR AREA OF A DWELLING UNIT, THE TWO OR MORE
 20-AMPERE SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY
 SECTION E3703.2, SHALL SERVE ALL WALL AND FLOOR
 RECEPTACLE OUTLETS COVERED BY SECTIONS E3901.2 AND
 E3901.4 AND THOSE RECEPTACLE OUTLETS PROVIDED FOR
 REFRIGERATION APPLIANCES. [210.52(B)(1)].
  
 4. CIRCUT 23 FOR LAUNDRY SHALL BE A MINIMUM OF 20 AMPS
 PER E3703.3.
 E3703.3 LAUNDRY CIRCUIT.
 A MINIMUM OF ONE 20-AMPERE-RATED BRANCH CIRCUIT SHALL
 BE PROVIDED FOR RECEPTACLES LOCATED IN THE LAUNDRY AREA
 AND SHALL SERVE ONLY RECEPTACLE OUTLETS LOCATED IN THE
 LAUNDRY AREA. [210.11(C)(2)].
  
 5. CONDUCTOR SIZING FOR THE WATER HEATER (2/40AMP) AND
 STOVE (2/60AMP) IS UNDERSIZED PER TABLE E3705.1.
  
 6. ARC FAULT NOTE ON PAGE E-1 SHALL INCLUDE KITCHENS.
 AFCI PROTECTION SHOWN IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING, POWER
 OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI
 AND GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8,
 210.12; FBC RE E3902.16; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
  
 7. PROVIDE SERVICE OUTLET AT CONDENSING UNIT PER
 E3901.12.
 E3901.12 HVAC OUTLET.
  
 8. EXTERIOR OUTLET REQUIRED AT FRONT OF STRUCTURE PER
 E3901.7.
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
 BALCONIES, DECKS, AND PORCHES THAT ARE ACCESSIBLE FROM
 INSIDE OF THE DWELLING UNIT SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE THAN 6 FEET, 6 INCHES (1981 MM) ABOVE
 THE BALCONY, DECK, OR PORCH SURFACE. [210.52(E)]
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  