2019-11-30 08:35:37PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE HAS BEEN ADJUSTED FRO 85000 TO 180405 BASED ON
 THE ICC BUILDING VALUATION TABLES.
  
 2. PROVIDE SURVEY AND DRAINAGE PLAN.
 FBC R401.3 SITE DRAINAGE
 PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3 DRAINAGE.
  
 PROVIDE SITE PLAN.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 3. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH
 OPENINGS AND DESIGN PRESSURES.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND
 EXTERIOR DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS.
  
 5. DESIGNER SHALL STATE INSULATION R VALUES ON PLAN.
 CEILINGS R-30 AND WALLS R-3.0.
 R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE).
 IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1,
 INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF
 SECTIONS R402.2.1 THROUGH R402.2.13.
  
 6. INSULATION ABOVE ATTIC SCUTTLE SHALL EQUAL
 SURRONDING R VALUE.
 R402.2.4 ACCESS HATCHES AND DOORS.
  
 7. ATTIC SCUTTLE SHALL HAVE WEATHER STRIPPING.
 R402.2.4 ACCESS HATCHES AND DOORS.
  
 8. LANSCAPE PLAN PAGE L INDICATES A THREE FOOT OVERHANG
 FOR ROOFING. NO STRUCTURAL DETAILS ARE PROVIDED. PLEASE
 CLARIFY.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 9. SHOW LOCATION OF ATTIC ACCESS ON PLANS. ACCESS SHALL
 COMPLY WITH M1305.1.3. SWITCHED LUMINARE AND SERVICE
 OUTLET ARE REQUIRED FOR MECH. EQUIPT. IN ATTICS.
 M1305.1.3.1 ELECTRICAL REQUIREMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY,
 INSERT CORRECTED PAGES INTO
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS
 DETACHED.
  
  
  
  
  