2019-11-30 08:35:37 | PLAN REVIEW - BUILDING |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. VALUE HAS BEEN ADJUSTED FRO 85000 TO 180405 BASED ON |
| THE ICC BUILDING VALUATION TABLES. |
| |
| 2. PROVIDE SURVEY AND DRAINAGE PLAN. |
| FBC R401.3 SITE DRAINAGE |
| PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| |
| PROVIDE SITE PLAN. |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. |
| |
| 3. PROVIDE WINDOW AND DOOR SCHEDULE. INCLUDE ROUGH |
| OPENINGS AND DESIGN PRESSURES. |
| FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS AND |
| EXTERIOR DOORS. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| |
| 5. DESIGNER SHALL STATE INSULATION R VALUES ON PLAN. |
| CEILINGS R-30 AND WALLS R-3.0. |
| R402.2 SPECIFIC INSULATION REQUIREMENTS (PRESCRIPTIVE). |
| IN ADDITION TO THE REQUIREMENTS OF SECTION R402.1, |
| INSULATION SHALL MEET THE SPECIFIC REQUIREMENTS OF |
| SECTIONS R402.2.1 THROUGH R402.2.13. |
| |
| 6. INSULATION ABOVE ATTIC SCUTTLE SHALL EQUAL |
| SURRONDING R VALUE. |
| R402.2.4 ACCESS HATCHES AND DOORS. |
| |
| 7. ATTIC SCUTTLE SHALL HAVE WEATHER STRIPPING. |
| R402.2.4 ACCESS HATCHES AND DOORS. |
| |
| 8. LANSCAPE PLAN PAGE L INDICATES A THREE FOOT OVERHANG |
| FOR ROOFING. NO STRUCTURAL DETAILS ARE PROVIDED. PLEASE |
| CLARIFY. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 9. SHOW LOCATION OF ATTIC ACCESS ON PLANS. ACCESS SHALL |
| COMPLY WITH M1305.1.3. SWITCHED LUMINARE AND SERVICE |
| OUTLET ARE REQUIRED FOR MECH. EQUIPT. IN ATTICS. |
| M1305.1.3.1 ELECTRICAL REQUIREMENTS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, |
| INSERT CORRECTED PAGES INTO |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS |
| DETACHED. |
| |
| |
| |
| |
| |