Date |
Text |
2019-12-30 14:26:01 | NONE OF THE INITIAL FAILED COMMENTS WERE ADDRESSED |
| DURING THIS PLAN REVIEW SUBMISSION. |
| ADDITIONALLY, THE OCCUPANT LOAD LISTED AS 336 PERSONS |
| DIRECTLY CONFLICTS WITH THE NUMBERS INDICATED ON THE |
| DRAWINGS. |
| A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED DURING PLAN RESUBMISSION. |
| |
| UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND/OR FIRE ALARM SYSTEM. |
| 13.3.2.7.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY |
| OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE |
| ASSEMBLY OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY |
| AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH NFPA 13 AS FOLLOWS (SEE ALSO 12.1.6, |
| 12.2.6, 12.3.2, AND 12.3.6 OF NFPA 101) |
| 13.7.2.2.1.1 EXISTING ASSEMBLY OCCUPANCIES WITH |
| OCCUPANT LOADS OF MORE THAN 300 AND ALL THEATERS WITH |
| MORE THAN ONE AUDIENCE-VIEWING ROOM SHALL BE PROVIDED |
| WITH AN APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| SECTION 13.7 AND 13.7.2.2, UNLESS OTHERWISE PERMITTED |
| BY 13.7.2.2.1.2, 13.7.2.2.1.3, OR 13.7.2.2.1.4. [101: |
| 13.3.4.1.1] |
| |
| FIXED SEATING PLAN DOES NOT MATCH OCCUPANCY TALLY OF |
| BAR SEATING CAPACITY. |
| 13.2.5.4.8 IN THE CASE OF SIDE BOUNDARIES FOR AISLE |
| ACCESSWAYS OR AISLES, OTHER THAN THOSE FOR NONFIXED |
| SEATING AT TABLES, THE CLEAR WIDTH SHALL BE MEASURED TO |
| BOUNDARY ELEMENTS SUCH AS WALLS, GUARDRAILS, HANDRAILS, |
| EDGES OF SEATING, TABLES, AND SIDE EDGES OF TREADS, AND |
| SAID MEASUREMENT SHALL BE MADE HORIZONTALLY TO THE |
| VERTICAL PROJECTION OF THE ELEMENTS, RESULTING IN THE |
| SMALLEST WIDTH MEASURED PERPENDICULARLY TO THE LINE OF |
| TRAVEL. |
| |
| NO INDICATION OF WHAT REPAIRS ARE BEING MADE TO BRING |
| TO CODE PER PERMIT# 19111016 SUBMITTAL. PLEASE PROVIDE |
| MATERIAL DATAT SHEETS FOR MATERIALS TO BE UTILIZED. |
| |
| NO INDICATION OF WHAT ELECTRICAL REPAIRS ARE TO BE MADE |
| TO BRING TO CODE PER PERMIT# 19111020 SUBMITTAL. (THIS |
| PERMIT CARD WAS INCLUDED IN SUBMISSION PACKET WITH NO |
| INFORMATION). |
| |
| PLEASE PROVIDE ACCURATE DIMENSIONS FOR EACH "FUNCTION |
| OF SPACE" AS WELL AS ACCURATE MEASUREMENTS FOR FIXED |
| SEATING TO ACCOUNT FOR OCCUPANT LOAD. OCCUPANCY NUMBERS |
| DID NOT MATCH INDICATED AREAS. |
| 10.14.3.4.3 LIFE SAFETY FLOOR PLANS. LIFE SAFETY FLOOR |
| PLANS OF EACH LEVEL SHALL BE PROVIDED WITH THE |
| FOLLOWING: |
| (1) OCCUPANT LOAD, EXIT LOCATION, EXIT CAPACITY, MAIN |
| EXIT/ NTRY, HORIZONTAL EXITS, TRAVEL DISTANCE AND EXIT |
| DISCHARGE |
| (2) FIRE AND SMOKE BARRIERS |
| (3) AREAS OF SMOKE PROTECTED ASSEMBLY OCCUPANCY |
| (4) SEPARATE SMOKE PROTECTED AREAS OR ZONES IF |
| APPLICABLE |
| (5) AREAS OF OTHER OCCUPANCY TYPE AND SEPARATIONS IF |
| REQUIRED |
| (6) UNPROTECTED VERTICAL OPENINGS, INCLUDING ATRIUMS, |
| COMMUNICATING SPACES, AND CONVENIENCE OPENINGS |
| (7) EVENT PLANS FOR EACH ANTICIPATED TYPE OF EVENT |
| DEPICTING THE FOLLOWING: |
| (A) SEATING CONFIGURATION |
| (B) EXHIBIT BOOTH LAYOUT |
| (C) STAGE LOCATION |
| (D) OCCUPANT LOAD, EXIT CAPACITY REQUIRED, EXITS |
| PROVIDED AND TRAVEL DISTANCE |
| (E) ANY FLOOR OR STAGE USE RESTRICTIONS |
| (F) PLAN AND/OR SECTION DRAWING INDICATING AREAS WHERE |
| THE ROOF CONSTRUCTION IS MORE THAN 50 FEET AND LIMITS |
| OF SPRINKLER PROTECTION. |
| (G) AREAS OF REFUGE- INTERIOR AND EXTERIOR [101: |
| 12.4.1.4.3] |
| |
| PER SECTION 7.2.1.4.3 DOOR LEAF ENCROACHMENT - DURING |
| ITS SWING, ANY DOOR LEAF IN A MEANS OF EGRESS SHALL |
| LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF |
| AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING |
| UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN 7-INCHES |
| INTO THE REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A |
| PASSAGEWAY, OR A LANDING, WHEN |
| FULLY OPEN. |
| |
| ALL EXTERIOR DOORS NOT FUNCTIONING AS EXITS SHALL BE |
| PERMANENTLY MARKED AND CLEARLY INDICATED AS, "NOT AN |
| EXIT." |
| |
| S.THOMAS |
| 561-804-4728 |
2019-12-12 14:22:26 | SEE 12/12/19 FRONT SCREEN NOTE. SAK |