2019-12-04 12:16:59 | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED DURING PLAN RESUBMISSION. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND/OR FIRE ALARM SYSTEM. |
| 13.3.2.7.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY |
| OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE |
| ASSEMBLY OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY |
| AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH NFPA 13 AS FOLLOWS (SEE ALSO 12.1.6, |
| 12.2.6, 12.3.2, AND 12.3.6 OF NFPA 101) |
| 13.7.2.2.1.1 EXISTING ASSEMBLY OCCUPANCIES WITH |
| OCCUPANT LOADS OF MORE THAN 300 AND ALL THEATERS WITH |
| MORE THAN ONE AUDIENCE-VIEWING ROOM SHALL BE PROVIDED |
| WITH AN APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH |
| SECTION 13.7 AND 13.7.2.2, UNLESS OTHERWISE PERMITTED |
| BY 13.7.2.2.1.2, 13.7.2.2.1.3, OR 13.7.2.2.1.4. [101: |
| 13.3.4.1.1] |
| |
| NO INDICATION OF BAR SEATING CAPACITY (FIXED SEATING). |
| 13.2.5.4.8 IN THE CASE OF SIDE BOUNDARIES FOR AISLE |
| ACCESSWAYS OR AISLES, OTHER THAN THOSE FOR NONFIXED |
| SEATING AT TABLES, THE CLEAR WIDTH SHALL BE MEASURED TO |
| BOUNDARY ELEMENTS SUCH AS WALLS, GUARDRAILS, HANDRAILS, |
| EDGES OF SEATING, TABLES, AND SIDE EDGES OF TREADS, AND |
| SAID MEASUREMENT SHALL BE MADE HORIZONTALLY TO THE |
| VERTICAL PROJECTION OF THE ELEMENTS, RESULTING IN THE |
| SMALLEST WIDTH MEASURED PERPENDICULARLY TO THE LINE OF |
| TRAVEL. |
| |
| NO INDICATION OF WHAT REPAIRS ARE BEING MADE TO BRING |
| TO CODE PER PERMIT# 19111016 SUBMITTAL. |
| |
| NO INDICATION OF WHAT ELECTRICAL REPAIRS ARE TO BE MADE |
| TO BRING TO CODE PER PERMIT# 19111020 SUBMITTAL. |
| |
| PLEASE PROVIDE ACCURATE DIMENSIONS FOR EACH "FUNCTION |
| OF SPACE" AS WELL AS ACCURATE MEASUREMENTS FOR FIXED |
| SEATING TO ACCOUNT FOR OCCUPANT LOAD. |
| 10.14.3.4.3 LIFE SAFETY FLOOR PLANS. LIFE SAFETY FLOOR |
| PLANS OF EACH LEVEL SHALL BE PROVIDED WITH THE |
| FOLLOWING: |
| (1) OCCUPANT LOAD, EXIT LOCATION, EXIT CAPACITY, MAIN |
| EXIT/ NTRY, HORIZONTAL EXITS, TRAVEL DISTANCE AND EXIT |
| DISCHARGE |
| (2) FIRE AND SMOKE BARRIERS |
| (3) AREAS OF SMOKE PROTECTED ASSEMBLY OCCUPANCY |
| (4) SEPARATE SMOKE PROTECTED AREAS OR ZONES IF |
| APPLICABLE |
| (5) AREAS OF OTHER OCCUPANCY TYPE AND SEPARATIONS IF |
| REQUIRED |
| (6) UNPROTECTED VERTICAL OPENINGS, INCLUDING ATRIUMS, |
| COMMUNICATING SPACES, AND CONVENIENCE OPENINGS |
| (7) EVENT PLANS FOR EACH ANTICIPATED TYPE OF EVENT |
| DEPICTING THE FOLLOWING: |
| (A) SEATING CONFIGURATION |
| (B) EXHIBIT BOOTH LAYOUT |
| (C) STAGE LOCATION |
| (D) OCCUPANT LOAD, EXIT CAPACITY REQUIRED, EXITS |
| PROVIDED AND TRAVEL DISTANCE |
| (E) ANY FLOOR OR STAGE USE RESTRICTIONS |
| (F) PLAN AND/OR SECTION DRAWING INDICATING AREAS WHERE |
| THE ROOF CONSTRUCTION IS MORE THAN 50 FEET AND LIMITS |
| OF SPRINKLER PROTECTION. |
| (G) AREAS OF REFUGE?INTERIOR AND EXTERIOR [101: |
| 12.4.1.4.3] |
| |