Plan Review Notes
Plan Review Notes For Permit 19111016
Permit Number 19111016
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-12-04 12:16:59A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 13.3.2.7.2 ANY BUILDING CONTAINING ONE OR MORE ASSEMBLY
 OCCUPANCIES WHERE THE AGGREGATE OCCUPANT LOAD OF THE
 ASSEMBLY OCCUPANCIES EXCEEDS 300 SHALL BE PROTECTED BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH NFPA 13 AS FOLLOWS (SEE ALSO 12.1.6,
 12.2.6, 12.3.2, AND 12.3.6 OF NFPA 101)
 13.7.2.2.1.1 EXISTING ASSEMBLY OCCUPANCIES WITH
 OCCUPANT LOADS OF MORE THAN 300 AND ALL THEATERS WITH
 MORE THAN ONE AUDIENCE-VIEWING ROOM SHALL BE PROVIDED
 WITH AN APPROVED FIRE ALARM SYSTEM IN ACCORDANCE WITH
 SECTION 13.7 AND 13.7.2.2, UNLESS OTHERWISE PERMITTED
 BY 13.7.2.2.1.2, 13.7.2.2.1.3, OR 13.7.2.2.1.4. [101:
 13.3.4.1.1]
  
 NO INDICATION OF BAR SEATING CAPACITY (FIXED SEATING).
 13.2.5.4.8 IN THE CASE OF SIDE BOUNDARIES FOR AISLE
 ACCESSWAYS OR AISLES, OTHER THAN THOSE FOR NONFIXED
 SEATING AT TABLES, THE CLEAR WIDTH SHALL BE MEASURED TO
 BOUNDARY ELEMENTS SUCH AS WALLS, GUARDRAILS, HANDRAILS,
 EDGES OF SEATING, TABLES, AND SIDE EDGES OF TREADS, AND
 SAID MEASUREMENT SHALL BE MADE HORIZONTALLY TO THE
 VERTICAL PROJECTION OF THE ELEMENTS, RESULTING IN THE
 SMALLEST WIDTH MEASURED PERPENDICULARLY TO THE LINE OF
 TRAVEL.
  
 NO INDICATION OF WHAT REPAIRS ARE BEING MADE TO BRING
 TO CODE PER PERMIT# 19111016 SUBMITTAL.
  
 NO INDICATION OF WHAT ELECTRICAL REPAIRS ARE TO BE MADE
 TO BRING TO CODE PER PERMIT# 19111020 SUBMITTAL.
  
 PLEASE PROVIDE ACCURATE DIMENSIONS FOR EACH "FUNCTION
 OF SPACE" AS WELL AS ACCURATE MEASUREMENTS FOR FIXED
 SEATING TO ACCOUNT FOR OCCUPANT LOAD.
 10.14.3.4.3 LIFE SAFETY FLOOR PLANS. LIFE SAFETY FLOOR
 PLANS OF EACH LEVEL SHALL BE PROVIDED WITH THE
 FOLLOWING:
 (1) OCCUPANT LOAD, EXIT LOCATION, EXIT CAPACITY, MAIN
 EXIT/ NTRY, HORIZONTAL EXITS, TRAVEL DISTANCE AND EXIT
 DISCHARGE
 (2) FIRE AND SMOKE BARRIERS
 (3) AREAS OF SMOKE PROTECTED ASSEMBLY OCCUPANCY
 (4) SEPARATE SMOKE PROTECTED AREAS OR ZONES IF
 APPLICABLE
 (5) AREAS OF OTHER OCCUPANCY TYPE AND SEPARATIONS IF
 REQUIRED
 (6) UNPROTECTED VERTICAL OPENINGS, INCLUDING ATRIUMS,
 COMMUNICATING SPACES, AND CONVENIENCE OPENINGS
 (7) EVENT PLANS FOR EACH ANTICIPATED TYPE OF EVENT
 DEPICTING THE FOLLOWING:
 (A) SEATING CONFIGURATION
 (B) EXHIBIT BOOTH LAYOUT
 (C) STAGE LOCATION
 (D) OCCUPANT LOAD, EXIT CAPACITY REQUIRED, EXITS
 PROVIDED AND TRAVEL DISTANCE
 (E) ANY FLOOR OR STAGE USE RESTRICTIONS
 (F) PLAN AND/OR SECTION DRAWING INDICATING AREAS WHERE
 THE ROOF CONSTRUCTION IS MORE THAN 50 FEET AND LIMITS
 OF SPRINKLER PROTECTION.
 (G) AREAS OF REFUGE?INTERIOR AND EXTERIOR [101:
 12.4.1.4.3]
  