2019-11-26 06:44:31 | 11/26/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE PLAN IS TOO SMALL TO READ NOTES, PLANS SHALL BE |
| DRAWN TO A MINIMUM 1/8" INCH SCALE PER THE WPB |
| AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING |
| PLANS. |
| 2. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| DIMENSIONS; AND ALL EXTERIOR ELEVATIONS IF APPLICABLE |
| PER THE FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| 3. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) |
| ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO |
| THE FBC SEC. 107.1 GENERAL. |
| 4. THE EXISTING PLAN ARE NOT CLEAR OF WHAT IS TO BE |
| DONE. DRAWING INDEX HAS SHEET 1.4 AND 1.5 ELEVATION BUT |
| THERE ARE NOT IN SET OF PLANS, PLEASE PROVIDE OR DELETE |
| FROM INDEX PER THE WPB AMENDMENTS TO THE FBC SEC. 107.1 |
| GENERAL. |
| 5. ON THE SCOPE OF WORK, IT SAYS ALTER BATHROOM TO |
| INCLUDE WASHING MACHINE, BUT THE MASTER IS LABELED AS |
| FUTURE ON SHEET 1.1 AND ON PLUMBING SHEET 1.2 THE 1/2 |
| BATH IN NOT SHOWN PLEASE CLARIFY PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.1 GENERAL. |
| 6. ISOMETRIC DRAWING WHICH WAS SUBMITTED DOES NOT SHOW |
| THE MASTER THAT IS LABELED AS FUTURE, IS IT PART OF THE |
| SCOPE AND IF IT IS PLEASE INCORPORATE IT IN THE |
| ISOMETRIC DRAWING. THE KITCHEN CAN NOT BE UP STREAM OF |
| A BATHROOM GROUP AND THE WASHING MACHINE CAN NOT BE AN |
| AAV ON 2" INCH, THE STANDPIPE HAS TO BE A 3" INCH |
| MINIMUM ACCORDING TO AAV MANUFACTURES SPECIFICATION. |
| W/M NEEDS TO BE DOWN STREAM OF THE BATHROOM GROUP AS |
| WELL AND YOU CAN COMBINE WITH K/S, PLEASE MAKE CHANGES |
| AS RESUBMIT WITH CLARITY PER THE WPB AMENDMENTS TO THE |
| FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING. |
| 7. YOU ARE WELCOME TO CONTACT ME TO DISCUSS THIS REVIEW |
| AND GO OVER CORRECTION. I AM AVAILABLE AS NOTED BELOW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |