Plan Review Notes
Plan Review Notes For Permit 19110914
Permit Number 19110914
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-26 06:44:3111/26/2019 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE PLAN IS TOO SMALL TO READ NOTES, PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8" INCH SCALE PER THE WPB
 AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF BUILDING
 PLANS.
 2. THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS IF APPLICABLE
 PER THE FBC WPB AMENDMENTS SEC. 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 3. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO
 THE FBC SEC. 107.1 GENERAL.
 4. THE EXISTING PLAN ARE NOT CLEAR OF WHAT IS TO BE
 DONE. DRAWING INDEX HAS SHEET 1.4 AND 1.5 ELEVATION BUT
 THERE ARE NOT IN SET OF PLANS, PLEASE PROVIDE OR DELETE
 FROM INDEX PER THE WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
 5. ON THE SCOPE OF WORK, IT SAYS ALTER BATHROOM TO
 INCLUDE WASHING MACHINE, BUT THE MASTER IS LABELED AS
 FUTURE ON SHEET 1.1 AND ON PLUMBING SHEET 1.2 THE 1/2
 BATH IN NOT SHOWN PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.1 GENERAL.
 6. ISOMETRIC DRAWING WHICH WAS SUBMITTED DOES NOT SHOW
 THE MASTER THAT IS LABELED AS FUTURE, IS IT PART OF THE
 SCOPE AND IF IT IS PLEASE INCORPORATE IT IN THE
 ISOMETRIC DRAWING. THE KITCHEN CAN NOT BE UP STREAM OF
 A BATHROOM GROUP AND THE WASHING MACHINE CAN NOT BE AN
 AAV ON 2" INCH, THE STANDPIPE HAS TO BE A 3" INCH
 MINIMUM ACCORDING TO AAV MANUFACTURES SPECIFICATION.
 W/M NEEDS TO BE DOWN STREAM OF THE BATHROOM GROUP AS
 WELL AND YOU CAN COMBINE WITH K/S, PLEASE MAKE CHANGES
 AS RESUBMIT WITH CLARITY PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING.
 7. YOU ARE WELCOME TO CONTACT ME TO DISCUSS THIS REVIEW
 AND GO OVER CORRECTION. I AM AVAILABLE AS NOTED BELOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  