Plan Review Notes For Permit 19110738 |
Permit Number |
19110738 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-11-18 18:59:25 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SYSTEM NUMBER W-2 ON PAGE 2 OF 3 OF PRODUCT | | APPROVAL FL9487-R5 FOR WOOD DECKS WITH MECHANICALLY | | ATTACHED INSULATION AND BONDED ROOF COVER HAS A MAXIMUM | | DESIGN PRESSURE OF -82.5 PSF. THIS TWO STORY BUILDING | | IS LOCATED IN EXPOSURE CATEGORY C WITH A VULT WIND | | SPEED OF 170 MPH. THE UPLIFT FOR ROOF ZONE 3 (CORNERS) | | IS -102 PSF AND EXCEEDS THE MAXIMUM DESIGN PRESSURE OF | | THE SPECIFIED SYSTEM. | | |
|