2019-11-25 08:53:58PLAN REVIEW - BUILDING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DFE HAS BEEN ESTABLISHED AS 10.0 FEET NAVD. PLAN
 PAGE SP-1 INDICATES FINISH FLOOR OF MAIN HOUSE SHALL BE
 9.0 FEET NAVD. PLEASE CORRECT.
  
 2. REFERENCE DETAIL 13/S4 AND DETAIL 1/S7. NO
 WATERPROOFING HAS BEEN INCORPORATED IN THE RETAINING
 WALL DESIGN. IF APPLICANT INTENDS TO PAINT THE WALLS
 YOU MAY CONSIDER WATERPROOFING.
  
 3. REFERENCE PLAN PAGE S-1 - TOP OF WALL ARCH, DETAIL
 REFERENCES DETAIL 2/S6. PROVIDE PLAN PAGE S-6.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  