2020-02-03 18:38:47PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 SUBMITTAL FOR THE EXTERIOR FOAM BAND AND TRIM IS
 DENIED.
  
 1) COMPLIED.
  
 2) THE DOCUMENTS THAT WERE SUBMITTED DO NOT ADDRESS THE
 PERFORMANCE REQUIREMENTS OF THE DESIGNER'S
 SPECIFICATIONS, SPECIFICALLY ASTM E2568, ICC-ES AC239
 AND ASTM E84. SUBMIT TEST REPORTS, ICC EVALUATION
 REPORTS OR OTHER APPROVED DATA FROM AN INDEPENDENT
 AGENCY TO SHOW COMPLIANCE. THE MANUFACTURER'S BROCHURES
 ARE NOT ACCEPTABLE. SEE FBC 2603.5
  
 3) THIS EVALUATION REPORT IS REQUIRED TO BE SUBMITTED
 FOR THE PAREX SYSTEM. NOTE: SEE ICC-ES EVALUATION
 REPORT ESR-2562.
 HTTPS://ICC-ES.ORG/REPORT-LISTING/ESR-2562/
  
 4) FBC 107.3.4 - THE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5) ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITAL.
  
 5) THE ICC EVALUATION REPORT FOR THE PARAX SYSTEM IS
 REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. FBC 107.3.4.1
  
  
  
  
  