Plan Review Notes For Permit 19110644 |
Permit Number |
19110644 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-12-18 17:05:38 | SUBMITTAL FOR THE EXTERIOR FOAM BAND AND TRIM IS | | DENIED. | | | | 1) THE PAREX EIFS WALL SYSTEM ON CONCRETE MASONRY, NOA | | NO. 12-0214.12 EXPIRED ON AUGUST 06,2017. THE DESIGNER | | OF RECORD HAS NOT REVIEWED AND APPROVED IT IN WRITING | | AS REQUIRED BY FBC 107.3.4. | | | | 2) THE DOCUMENTS THAT WERE SUBMITTED DO NOT ADDRESS THE | | PERFORMANCE REQUIREMENTS OF THE DESIGNER'S | | SPECIFICATIONS, SPECIFICALLY ASTM E2568, ICC-ES AC239 | | AND ASTM E84. SUBMIT TEST REPORTS, ICC EVALUATION | | REPORTS OR OTHER APPROVED DATA FROM AN INDEPENDENT | | AGENCY TO SHOW COMPLIANCE. THE MANUFACTURER'S BROCHURES | | ARE NOT ACCEPTABLE. SEE FBC 2603.5 | | | | 3) NOTE: SEE ICC-ES EVALUATION REPORT ESR-2562. |
|