Plan Review Notes
Plan Review Notes For Permit 19110644
Permit Number 19110644
Review Stop B
Sequence Number 2
Notes
Date Text
2019-12-18 17:05:38SUBMITTAL FOR THE EXTERIOR FOAM BAND AND TRIM IS
 DENIED.
  
 1) THE PAREX EIFS WALL SYSTEM ON CONCRETE MASONRY, NOA
 NO. 12-0214.12 EXPIRED ON AUGUST 06,2017. THE DESIGNER
 OF RECORD HAS NOT REVIEWED AND APPROVED IT IN WRITING
 AS REQUIRED BY FBC 107.3.4.
  
 2) THE DOCUMENTS THAT WERE SUBMITTED DO NOT ADDRESS THE
 PERFORMANCE REQUIREMENTS OF THE DESIGNER'S
 SPECIFICATIONS, SPECIFICALLY ASTM E2568, ICC-ES AC239
 AND ASTM E84. SUBMIT TEST REPORTS, ICC EVALUATION
 REPORTS OR OTHER APPROVED DATA FROM AN INDEPENDENT
 AGENCY TO SHOW COMPLIANCE. THE MANUFACTURER'S BROCHURES
 ARE NOT ACCEPTABLE. SEE FBC 2603.5
  
 3) NOTE: SEE ICC-ES EVALUATION REPORT ESR-2562.