2019-11-18 14:44:27 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY FIRE |
| CODES. |
| |
| IT APPEARS THAT THIS MAY BE FORE DIESEL FUEL. PLEASE |
| CONFIRM. |
| |
| THE INSTALLATION SHALL COMPLY WITH NFPA 30, FLAMMABLE |
| AND COMBUSTIBLE LIQUIDS CODE, 2015 EDITION. |
| |
| PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDEMENT AND |
| COMPLIANCE. |
| |
| |
| |
| |
| 2) THERE ARE NO DETAILS OF THE DEPTH AND TYPE OF COVER |
| OVER. |
| |
| PER NFPA 30 |
| |
| 27.6.5 INSTALLATION OF UNDERGROUND PIPING. |
| 27.6.5.1 UNDERGROUND PIPING SHALL BE INSTALLED ON AT |
| LEAST |
| 6 IN. (150 MM) OF WELL-COMPACTED BEDDING MATERIAL. |
| 27.6.5.2 IN AREAS SUBJECT TO VEHICLE TRAFFIC, THE PIPE |
| TRENCH |
| SHALL BE DEEP ENOUGH TO PERMIT A COVER OF AT LEAST 18 |
| IN. |
| (450 MM) OF WELL-COMPACTED BACKFILL MATERIAL AND |
| PAVEMENT. |
| 27.6.5.3 IN PAVED AREAS WHERE A MINIMUM 2 IN. (50 MM) |
| OF |
| ASPHALT IS USED, BACKFILL BETWEEN THE PIPE AND THE |
| ASPHALT SHALL |
| BE PERMITTED TO BE REDUCED TO 8 IN. (200 MM) MINIMUM. |
| 27.6.5.4 IN PAVED AREAS WHERE A MINIMUM 4 IN. (100 MM) |
| OF |
| REINFORCED CONCRETE IS USED, BACKFILL BETWEEN THE PIPE |
| AND THE |
| ASPHALT SHALL BE PERMITTED TO BE REDUCED TO 4 IN. (100 |
| MM) |
| MINIMUM. |
| 27.6.5.5 IN AREAS NOT SUBJECT TO VEHICLE TRAFFIC, THE |
| PIPE TRENCH |
| SHALL BE DEEP ENOUGH TO PERMIT A COVER OF AT LEAST 6 |
| IN. |
| (150 MM) OF WELL-COMPACTED BACKFILL MATERIAL. |
| 27.6.5.6 A GREATER BURIAL DEPTH SHALL BE PROVIDED WHEN |
| REQUIRED |
| BY THE MANUFACTURER?S INSTRUCTIONS OR WHERE FROST |
| CONDITIONS |
| ARE PRESENT. |
| 27.6.5.7 PIPING WITHIN THE SAME TRENCH SHALL BE |
| SEPARATED |
| HORIZONTALLY BY AT LEAST TWO PIPE DIAMETERS. SEPARATION |
| NEED |
| NOT EXCEED 9 IN. (230 MM). |
| 27.6.5.8 TWO OR MORE LEVELS OF PIPING WITHIN THE SAME |
| TRENCH |
| SHALL BE SEPARATED VERTICALLY BY A MINIMUM 6 IN. (150 |
| MM) OF |
| WELL-COMPACTED BEDDING MATERIAL. |
| |
| PLEASE PROVIDE SEPCIFIC DETAILS. |
| |
| |
| |
| 3) THERE ARE AREAS INDICATED WITH CONCRETE ENCASEMENT. |
| |
| PLEASE PROVIDE THE SPECIFIC DETAILS REGARDING THESE |
| AREAS AND THE SPECIFIC DETAILS OF THE ENCASEMENT. |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |