Plan Review Notes
Plan Review Notes For Permit 19110641
Permit Number 19110641
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-11-18 14:44:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE ARE NO INDICATIONS OF COMPLIANCE WITH ANY FIRE
 CODES.
  
 IT APPEARS THAT THIS MAY BE FORE DIESEL FUEL. PLEASE
 CONFIRM.
  
 THE INSTALLATION SHALL COMPLY WITH NFPA 30, FLAMMABLE
 AND COMBUSTIBLE LIQUIDS CODE, 2015 EDITION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDEMENT AND
 COMPLIANCE.
  
  
  
  
 2) THERE ARE NO DETAILS OF THE DEPTH AND TYPE OF COVER
 OVER.
  
 PER NFPA 30
  
 27.6.5 INSTALLATION OF UNDERGROUND PIPING.
 27.6.5.1 UNDERGROUND PIPING SHALL BE INSTALLED ON AT
 LEAST
 6 IN. (150 MM) OF WELL-COMPACTED BEDDING MATERIAL.
 27.6.5.2 IN AREAS SUBJECT TO VEHICLE TRAFFIC, THE PIPE
 TRENCH
 SHALL BE DEEP ENOUGH TO PERMIT A COVER OF AT LEAST 18
 IN.
 (450 MM) OF WELL-COMPACTED BACKFILL MATERIAL AND
 PAVEMENT.
 27.6.5.3 IN PAVED AREAS WHERE A MINIMUM 2 IN. (50 MM)
 OF
 ASPHALT IS USED, BACKFILL BETWEEN THE PIPE AND THE
 ASPHALT SHALL
 BE PERMITTED TO BE REDUCED TO 8 IN. (200 MM) MINIMUM.
 27.6.5.4 IN PAVED AREAS WHERE A MINIMUM 4 IN. (100 MM)
 OF
 REINFORCED CONCRETE IS USED, BACKFILL BETWEEN THE PIPE
 AND THE
 ASPHALT SHALL BE PERMITTED TO BE REDUCED TO 4 IN. (100
 MM)
 MINIMUM.
 27.6.5.5 IN AREAS NOT SUBJECT TO VEHICLE TRAFFIC, THE
 PIPE TRENCH
 SHALL BE DEEP ENOUGH TO PERMIT A COVER OF AT LEAST 6
 IN.
 (150 MM) OF WELL-COMPACTED BACKFILL MATERIAL.
 27.6.5.6 A GREATER BURIAL DEPTH SHALL BE PROVIDED WHEN
 REQUIRED
 BY THE MANUFACTURER?S INSTRUCTIONS OR WHERE FROST
 CONDITIONS
 ARE PRESENT.
 27.6.5.7 PIPING WITHIN THE SAME TRENCH SHALL BE
 SEPARATED
 HORIZONTALLY BY AT LEAST TWO PIPE DIAMETERS. SEPARATION
 NEED
 NOT EXCEED 9 IN. (230 MM).
 27.6.5.8 TWO OR MORE LEVELS OF PIPING WITHIN THE SAME
 TRENCH
 SHALL BE SEPARATED VERTICALLY BY A MINIMUM 6 IN. (150
 MM) OF
 WELL-COMPACTED BEDDING MATERIAL.
  
 PLEASE PROVIDE SEPCIFIC DETAILS.
  
  
  
 3) THERE ARE AREAS INDICATED WITH CONCRETE ENCASEMENT.
  
 PLEASE PROVIDE THE SPECIFIC DETAILS REGARDING THESE
 AREAS AND THE SPECIFIC DETAILS OF THE ENCASEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]