Plan Review Notes For Permit 19110637 |
Permit Number |
19110637 |
|
Review Stop |
NFIP |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-06 11:19:14 | THIS PROJECT HAS BEEN DETERMINED TO NOT REQUIRE | | SUBSTANTIAL IMPROVEMENT. | | FLOOD PROOFING AND FLOOD GATE WERE DONE TO REQUIREMENTS | | AS IF THEY WERE SUBSTANTIALLY IMPROVING. | | | | $16,424,316.00 MARKET VALUE STRUCTURE ONLY | | $2,400,000.00 COST OF IMPROVMENT | | | | RATIO=15% | | | | | 2019-12-12 15:37:28 | OK - PRE-CONSTRUCTION ELEVATION CERTIFICATE ADDED TP | | PROJECTDOX SUPPORTING DOCUMENTS. | | | | | | THE BASE FLOOD ELEVATION(BFE) WILL BE 12' NAVD. | | DESIGN FLOOD ELEVATION WILL BE 14' NAVD SINCE WE HAVE A | | 2' FREEBOARD. | | | | PROVISO: | | 1) PROVIDE ENGINEERED FLOODPROOFING AS SUBMITTAL TO | | PERMIT 19110637 | | THE FLOOD PROOFING WILL ONLY NEED TO EXTEND TO 14' | | NAVD. | | 2) ENGINEER TO PROVIDE FLOODPROOFING CERTIFICATE FOR | | THE DEISGN PROVIDED. | | 3) PROVIDE FINAL ELAVATION CERTIFICATE UPON COMPLETION | | OF CONSTRUCTION. | | |
|