Plan Review Notes
Plan Review Notes For Permit 19110637
Permit Number 19110637
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2021-12-06 11:19:14THIS PROJECT HAS BEEN DETERMINED TO NOT REQUIRE
 SUBSTANTIAL IMPROVEMENT.
 FLOOD PROOFING AND FLOOD GATE WERE DONE TO REQUIREMENTS
 AS IF THEY WERE SUBSTANTIALLY IMPROVING.
  
 $16,424,316.00 MARKET VALUE STRUCTURE ONLY
 $2,400,000.00 COST OF IMPROVMENT
  
 RATIO=15%
  
  
2019-12-12 15:37:28OK - PRE-CONSTRUCTION ELEVATION CERTIFICATE ADDED TP
 PROJECTDOX SUPPORTING DOCUMENTS.
  
  
 THE BASE FLOOD ELEVATION(BFE) WILL BE 12' NAVD.
 DESIGN FLOOD ELEVATION WILL BE 14' NAVD SINCE WE HAVE A
 2' FREEBOARD.
  
 PROVISO:
 1) PROVIDE ENGINEERED FLOODPROOFING AS SUBMITTAL TO
 PERMIT 19110637
 THE FLOOD PROOFING WILL ONLY NEED TO EXTEND TO 14'
 NAVD.
 2) ENGINEER TO PROVIDE FLOODPROOFING CERTIFICATE FOR
 THE DEISGN PROVIDED.
 3) PROVIDE FINAL ELAVATION CERTIFICATE UPON COMPLETION
 OF CONSTRUCTION.
  