Date |
Text |
2019-12-12 10:33:06 | ?REVIEWS COMPLETED UNDER APPLICATION 18120436.? |
| |
| |
| THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| |
| 1) SHEET FP 001 - THERE ARE INDICATIONS OF FIRE |
| SPRINKLER WORK. THERE ARE NO INDICATIONS THAT THE WORK |
| SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS |
| BY CERTIFIED FIRE SPRINKLER CONTRACTORS. |
| |
| ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE |
| PERMIT AND SHOP DRAWINGS. |
| |
| |
| |
| 2) SHEET FP 101 A - THERE ARE INDICATIONS OF FIRE |
| SPRINKLER WORK IN THE SOUTH, ADULT SECTION. THERE ARE |
| NO INDICATIONS OF WORK IN THE NORTH, CHILD SECTION. |
| |
| ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE |
| PERMIT AND SHOP DRAWINGS. |
| |
| |
| |
| 3) SHEET E 001 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| DEVICES, EQUIPMENT, OR WORK OF THE FIRE ALARM SYSTEM. |
| |
| ANY WORK ON THE FIRE ALARM, DEMO AND/OR NEW |
| INSTALLTIONS SHALL BE DONE UNDER SEPARATE PERMIT AND |
| SHOP DRAWING BY CERTIFIED FIRE ALARM CONTRACTORS. |
| |
| |
| 4) SHEET A 575 - THERE ARE INDICATIONS OF CARD READERS |
| AND CONTROLLED EGRESS WITHIN THE DOOR SCHEDULE. |
| |
| ALL INSTALL INVOLVING EGRESS SHALL COMPLY WITH NFPA |
| 101, CHAPTER 7, MEANS OF EGRESS AS APPLICABLE. |
| |
| ANY WORK OF CARD READERS AND/OR CONTROLLED EGRESS SHALL |
| BE DONE UNDER PERMIT AND SEPARATE SHOP DRAWINGS. |
| |
| |
| |
| 5) SHEET G 100 - THERE ARE NO INDICATIONS UNDER DEMO |
| AND/OR OTHER APPLICABLE AREAS REGARDING THE LIFE SAFETY |
| SYSTEM BEING MAINTAINED. |
| |
| COMPLIED - NOTE ADDED |
| |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |