Plan Review Notes For Permit 19110612 |
Permit Number |
19110612 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-11-14 06:14:12 | 1) A PLUMBING CONTRACTOR CANNOT INSTALL A BACKFLOW | | DEVICE ON A FIRE PROTECTION SYSTEM UNLESS THE | | CONTRACTOR IS LICENSED AS A FIRE PROTECTION CONTRACTOR | | I, II OR V IN ACCORDANCE WITH FL. STATUTE 633.102, | | 633.336. IF YOU ARE LICENSED AS ONE OF THE | | AFOREMENTIONED CONTRACTOR TYPES, SUBMIT A COPY OF YOUR | | CURRENT FIRE PROTECTION CONTRACTOR LICENSENE. | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE BACKFLOW DEVICE. WPB AMEND. TO | | FBC SEC. 107.2.1. | | 3) ALL BACKFLOW DEVICES MUST BE LEAD FREE AND BE ON THE | | APPROVED LIST OF DEVICES OF THE UNIVERSITY OF SOUTHERN | | CALIFORNIA FOUNDATION FOR CROSS-CONNECTION CONTROL AND | | HYDRAULIC RESEARCH PER THE CITY OF WEST PALM BEACH | | CROSS CONNECTION CONTROL MANUAL AS ADOPTED BY | | ORDINANCE. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|