Plan Review Notes
Plan Review Notes For Permit 19110612
Permit Number 19110612
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-14 06:14:121) A PLUMBING CONTRACTOR CANNOT INSTALL A BACKFLOW
 DEVICE ON A FIRE PROTECTION SYSTEM UNLESS THE
 CONTRACTOR IS LICENSED AS A FIRE PROTECTION CONTRACTOR
 I, II OR V IN ACCORDANCE WITH FL. STATUTE 633.102,
 633.336. IF YOU ARE LICENSED AS ONE OF THE
 AFOREMENTIONED CONTRACTOR TYPES, SUBMIT A COPY OF YOUR
 CURRENT FIRE PROTECTION CONTRACTOR LICENSENE.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE BACKFLOW DEVICE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) ALL BACKFLOW DEVICES MUST BE LEAD FREE AND BE ON THE
 APPROVED LIST OF DEVICES OF THE UNIVERSITY OF SOUTHERN
 CALIFORNIA FOUNDATION FOR CROSS-CONNECTION CONTROL AND
 HYDRAULIC RESEARCH PER THE CITY OF WEST PALM BEACH
 CROSS CONNECTION CONTROL MANUAL AS ADOPTED BY
 ORDINANCE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  