2019-12-10 09:33:33 | PLAN REVIEW - BUILDING |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. STRUCTURE QUALIFIES AS A SUBSTANTIAL IMPROVEMENT. |
| SEE NFIP REVIEW FOR COMMENTS. |
| |
| 2. ON PLAN PAGE A-200 CHANGE OCCUPANCY CLASIFICATION |
| FROM R2 TO R3. |
| 310.5 RESIDENTIAL GROUP R-3. |
| RESIDENTIAL GROUP R-3 OCCUPANCIES WHERE THE OCCUPANTS |
| ARE PRIMARILY PERMANENT IN NATURE AND NOT CLASSIFIED AS |
| GROUP R-1, R-2, R-4 OR I, |
| |
| 3. ON PLAN P-AGE A-200 CHANGE LEVEL OF ALTERATION FROM |
| LEVEL 1 TO LEVEL 2. |
| 504.1 SCOPE. |
| LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF |
| SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR |
| WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, |
| OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT. |
| |
| 4. PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY DESIGNER. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 5. NOTE ON PLAN PAGE A-200 STATES SQUARE FOOTAGE TO |
| REMAIN THE SAME. APPLICATION STATES THE SOW WILL |
| INCLUDE AN ADDITION. PLANS INDICATE ADDITIONAL SQUARE |
| FOOTAGE UNDER AIR. PLEASE CLARIFY. |
| |
| 6. PROVIDE ENERGY SUBMITTAL. |
| ENERGY SUBMITTAL |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. |
| |
| 7. DESIGNER TO STATE INSULATION R-VALUES ON PLAN. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 8. PROVIDE DETAIL FOR TYPICAL WOOD FRAMED WALL. SEE |
| DETAILS 4&5 S-4. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 9. PROVIDE LINTEL SCHEDULE. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 10. ROOFING PERMIT REQUIRED. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |
| |
| |