2019-11-18 06:53:29 | 11/19/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| EXISTING GAS. A FULL EVALUATION OF ALL GAS EQUIPMENT |
| WILL BE DONE, IF NOT TO CODE, IT MAY NEED TO BE BOUT UP |
| TO CODE COMPLIANCE PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 2. PLEASE SHOW AND LABEL SHUTOFF VALVES, UNIONS, DRIP |
| LEGS AND REGULATORS ON ISOMETRIC PER THE 2017 FBC FG |
| SEC. 409.4. |
| 3. BTU'S OF GENERATOR IS WRONG PLEASE REFER TO |
| MANUFACTURES SPECIFICATION AND CORRECT AND RECALCULATE |
| TOTAL LOAD PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 4. LONGEST RUN IS NOT 35' PLEASE RECALCULATE AND UPDATE |
| ON ISOMETRIC PLANS PER THE WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| (CLOTHES DRYERS AND RANGE) OR 2017 FBC RES. SEC. |
| G2407.1 AND G2439.4. |
| 6. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| 7. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2017 |
| FBC RES. SEC. G2413.2 AND G2404.3. |
| 8. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A |
| ROOF, IS SO PLEASE PROVIDE MANUFACTURES RECOMMENDATION |
| FOR A VENTILATION HOOD PER THE 2017 FBC RES. SEC. |
| G2408.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |