Plan Review Notes For Permit 19110402 |
Permit Number |
19110402 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-06-04 09:44:24 | 3RD REVIEW FBC-2017 MECHANICAL | | PERMIT-19110402 | | | | CODES IN EFFECT: | | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | EDITION 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) NOT ENOUGH INFORMATION INCLUDED IN THIS SUBMISSION | | TO DO THIS GAS LINE REVIEW: PLEASE SHOW A DETAIL OF THE | | NEW PIPE CONNECTION INTO THE EXISTING SYSTEM. WHAT IS | | THE PRESSURE OF THE EXISTING SYSTEM? FBC FS 107.2.1, | | FBC RES G2412.4 | | | | 2) PLEASE SHOW THE LOCATION OF THE REGULATOR, ALSO | | PROVIDE SPECS ON THE REGULATOR USED. FBC RES G2421.1 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN | | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS | | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | UPDATED. | | | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | | | |
|