Plan Review Notes
Plan Review Notes For Permit 19110402
Permit Number 19110402
Review Stop B
Sequence Number 3
Notes
Date Text
2020-05-15 14:43:17PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD AND ANCHORING PLANS ARE REQUIRED
 TO HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
  
 2) THE GENERATOR PAD ENGINEERING THAT WAS SUBMITTED IS
 NOT FOR THE GENERAC 16KW GENERATOR SPECS. THAT WERE
 SUBMITTED. THE GENERATOR IN THE SPECIFICATIONS IS 409
 LBS AND DOES NOT MEET THE WEIGHT REQUIRED BY THE PAD
 ENGINEERING. THE SIZE AND WEIGHT OF THE GENERATOR HAS
 TO MATCH THE REQUIREMENTS OF THE PAD ENGINEERING. FBC
 107.2.1
  