2019-11-18 06:59:39 | 11/19/2019 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON THE ELECTRICAL SHOW A 16 KW CIRCLED AND ON THE |
| PLUMBING IT HAS A 22 KW WHICH ONE IS IT HAS THE HAVE |
| DIFFERENT BTU'S, PLEASE CLARIFY PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| 2. PLEASE LABEL SHUTOFF VALVES, UNIONS, DRIP LEGS, |
| BTU'S OF GENERATOR AND REGULATORS (IF NEEDED PER UNIT) |
| ON ISOMETRIC PER THE 2017 FBC FG SEC. 409.4. |
| 3. THE PHYSICAL ADDRESS OF THE PROJECT MUST BE ON PLANS |
| IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP CODE PER |
| THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS |
| 4. SUBMIT COPIES OF THE SIZING TABLE USED IN THE DESIGN |
| FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS OF |
| PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM PER THE 2017 FBC FG SEC. 402. |
| 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC RES. |
| SEC. G2413.2. |
| 7. THE CITY RECORDS INDICATE AN EXISTING GAS METER. THE |
| BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO |
| THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| PER THE 2017 FBC RES. SECS. G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| 8. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1 |
| GENERAL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |