2020-02-10 11:28:28 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #19110320 |
| 2/10/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED |
| |
| 1) NO ADDITIONAL INFORMATION HAS BEEN PROVIDED ON THE |
| PLANS TO VERIFY THAT THE FACILITY IS EQUIPPED TO INSURE |
| AMBIENT AIR TEMPERTURES FOR RESIDENTS WILL BE |
| MAINTAINED AT OR BELOW 81 DEGREES FAHRENHEIT FOR A |
| MINIMUM OF 96 HOURS IN THE EVENT OF THE LOSS OF PRIMARY |
| ELECTRICAL POWER- SECTION 59A-.025 (1)(A) FAC. PLEASE |
| NOTE THAT NEW THROUGH-THE-WALL AC SYSTEMS FOR RESIDENT |
| ROOMS ARE SHOWN ON THE PLANS HOWEVER IT IS NOT KNOW IF |
| THESE SYSTEMS ARE CONNECTED TO THE EMERGENCY POWER |
| SOURCE. SECONDLY THE EMERGENCY CONTROL PLAN SUBMITTAL |
| TO PALM BEACH INDICATES THAT 160 BEDS IN THE COMMON |
| AREA(S) WILL BE PROVIDED WITH THE REQUIRED COOLING |
| UNDER EMERGENCY POWER. PLEASE SHOW THESE COMMON |
| AREA(S)AND THEIR RESPECTIVE AC SYSTEMS ON THE PLANS. |
| |
| 2) SHEETS M1 & M2: PROVIDE CONDESNATE DISPOSAL PLANS |
| FOR THE NEW THOUGH-THE-WALL AC SYSTEMS. SHOW PIPING |
| RUNS AND DISCHARGE LOCATIONS- SECTION 307.2.1 FBC M |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |