2020-02-07 14:51:42 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| IT SEEMS THERE WAS NO RESPONSE PROVIDED FROM THE LAST |
| REVIEW. PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. BASED ON RECORDS SEARCH, IT APPEARS A GENERATOR |
| PERMIT FOR A PERMANENTLY INSTALLED GENERATOR THAT IS |
| MAINTAINED AT THE FACILITY IN COMPLIANCE WITH THE |
| FLORIDA ADMINISTRATIVE CODE HAS NOT BEEN OBTAINED FOR |
| THIS SITE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS. |
| FAC 59A-36.025(1)(A) |
| 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, ALTERNATE POWER SOURCES, UNDERGROUND |
| OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE |
| AND FEED TO ANY SUB-PANEL(S) AND/OR TRANSFER SWICHES. |
| SHOW GEC SIZE AND SYSTEM. NEC 215.5, 230, 250.50, |
| 250.94, 408.30 |
| 4. PROVIDE LOAD CALCULATION FOR ITEMS THAT ARE FED FROM |
| THE GENERATOR. NEC 220, 701.4 |
| 5. THE GENERATOR IDENTIFIED IN THE EMERGENCY |
| ENVIRONMENTAL CONTROL PLAN AND IN THE GENERATOR |
| INFORMATION SHEET IS DIFFERENT THAN WHAT IS SPECIFIED |
| IN THE SUPPORTING DOCUMENTATION UNDER LOSS OF |
| ELECTRICAL, FACILITY GENERATOR. WHICH IS IT? 177 KW OR |
| 60 KW? PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |