2020-02-07 14:51:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 IT SEEMS THERE WAS NO RESPONSE PROVIDED FROM THE LAST
 REVIEW. PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. BASED ON RECORDS SEARCH, IT APPEARS A GENERATOR
 PERMIT FOR A PERMANENTLY INSTALLED GENERATOR THAT IS
 MAINTAINED AT THE FACILITY IN COMPLIANCE WITH THE
 FLORIDA ADMINISTRATIVE CODE HAS NOT BEEN OBTAINED FOR
 THIS SITE. PROVIDE CLARIFICATIONS AND/OR CORRECTIONS.
 FAC 59A-36.025(1)(A)
 3. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, ALTERNATE POWER SOURCES, UNDERGROUND
 OR OVERHEAD SERVICE, WIRE AND BREAKER SIZES FOR SERVICE
 AND FEED TO ANY SUB-PANEL(S) AND/OR TRANSFER SWICHES.
 SHOW GEC SIZE AND SYSTEM. NEC 215.5, 230, 250.50,
 250.94, 408.30
 4. PROVIDE LOAD CALCULATION FOR ITEMS THAT ARE FED FROM
 THE GENERATOR. NEC 220, 701.4
 5. THE GENERATOR IDENTIFIED IN THE EMERGENCY
 ENVIRONMENTAL CONTROL PLAN AND IN THE GENERATOR
 INFORMATION SHEET IS DIFFERENT THAN WHAT IS SPECIFIED
 IN THE SUPPORTING DOCUMENTATION UNDER LOSS OF
 ELECTRICAL, FACILITY GENERATOR. WHICH IS IT? 177 KW OR
 60 KW? PROVIDE CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  