Date |
Text |
2019-12-27 14:33:07 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19110320 |
| 12/27/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED |
| |
| 1) THE NEW DOCUMENTS SUBMITTED- EMERGENCY PLAN APPROVAL |
| LETTER FROM THE PB DEPT. OF PUBLIC SAFETY DIVISION OF |
| EMERGENCY MANAGEMENT, AND THE AHCA SAMPLE FORMAT FOR |
| PLAN SUBMISSION- APPEAR TO INDICATE THAT A NEW |
| EMERGENCY GENERATOR IS TO BE INSTALLED AT THE FACILITY. |
| PLEASE ACKNOWLEDGE. WEST PALM BEACH BUILDING DEPARTMENT |
| PERMIT RECORDS DO NOT INDICATE THAT AN EMERGENCY |
| GENERATOR PERMIT WAS EVER ISSUED FOR THE FACILITY. |
| FINAL APPROVAL OF THE MECHANICAL COOLING AND HEATING |
| SYSTEM INSTALLATIONS AT THE FACILITY UNDER THIS PERMIT |
| IS ON HOLD PENDING CLARIFICATION OF EMERGENCY GENERATOR |
| INSTALLATION. PLEASE NOTE THAT A SEPARATE PERMIT IS |
| REQUIRED. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |
| |