Plan Review Notes
Plan Review Notes For Permit 19110320
Permit Number 19110320
Review Stop M
Sequence Number 2
Notes
Date Text
2019-12-27 14:33:072ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19110320
 12/27/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1) THE NEW DOCUMENTS SUBMITTED- EMERGENCY PLAN APPROVAL
 LETTER FROM THE PB DEPT. OF PUBLIC SAFETY DIVISION OF
 EMERGENCY MANAGEMENT, AND THE AHCA SAMPLE FORMAT FOR
 PLAN SUBMISSION- APPEAR TO INDICATE THAT A NEW
 EMERGENCY GENERATOR IS TO BE INSTALLED AT THE FACILITY.
 PLEASE ACKNOWLEDGE. WEST PALM BEACH BUILDING DEPARTMENT
 PERMIT RECORDS DO NOT INDICATE THAT AN EMERGENCY
 GENERATOR PERMIT WAS EVER ISSUED FOR THE FACILITY.
 FINAL APPROVAL OF THE MECHANICAL COOLING AND HEATING
 SYSTEM INSTALLATIONS AT THE FACILITY UNDER THIS PERMIT
 IS ON HOLD PENDING CLARIFICATION OF EMERGENCY GENERATOR
 INSTALLATION. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  