Plan Review Notes
Plan Review Notes For Permit 19110320
Permit Number 19110320
Review Stop P
Sequence Number 1
Notes
Date Text
2019-12-03 10:31:511ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.2 STANDARD
 ROLL-IN TYPE SHOWER COMPARTMENTS. IN STANDARD ROLL-IN
 TYPE SHOWER COMPARTMENTS, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE THE GRAB BAR,
 BUT NO HIGHER THAN 48 INCHES ABOVE THE SHOWER FLOOR.
 WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL
 ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27
 INCHES MAXIMUM FROM THE SEAT WALL. AND
 608.6 SHOWER SPRAY UNIT AND WATER. A SHOWER SPRAY UNIT
 WITH A HOSE 59 INCHES LONG MINIMUM THAT CAN BE USED
 BOTH AS A FIXED-POSITION SHOWER HEAD AND AS A HAND-HELD
 SHOWER SHALL BE PROVIDED. THE SHOWER SPRAY UNIT SHALL
 HAVE AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF. IF
 AN ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS
 USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT
 THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER
 WATER THAT IS 120?F (49?C) MAXIMUM
  
 2. PROVIDE SHUT OF VALVE FOR ALL DOWN FED WATER LINE
 CAN BE ON THE BRANCH FROM MAIN LINE. PER FBC PL 606.1
 (5)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  