2019-12-03 10:31:51 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. PLEASE SHOW COMPLIANCE WITH FBC ACC 608.5.2 STANDARD |
| ROLL-IN TYPE SHOWER COMPARTMENTS. IN STANDARD ROLL-IN |
| TYPE SHOWER COMPARTMENTS, THE CONTROLS, FAUCETS, AND |
| SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE THE GRAB BAR, |
| BUT NO HIGHER THAN 48 INCHES ABOVE THE SHOWER FLOOR. |
| WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND |
| SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL |
| ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27 |
| INCHES MAXIMUM FROM THE SEAT WALL. AND |
| 608.6 SHOWER SPRAY UNIT AND WATER. A SHOWER SPRAY UNIT |
| WITH A HOSE 59 INCHES LONG MINIMUM THAT CAN BE USED |
| BOTH AS A FIXED-POSITION SHOWER HEAD AND AS A HAND-HELD |
| SHOWER SHALL BE PROVIDED. THE SHOWER SPRAY UNIT SHALL |
| HAVE AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF. IF |
| AN ADJUSTABLE-HEIGHT SHOWER HEAD ON A VERTICAL BAR IS |
| USED, THE BAR SHALL BE INSTALLED SO AS NOT TO OBSTRUCT |
| THE USE OF GRAB BARS. SHOWER SPRAY UNITS SHALL DELIVER |
| WATER THAT IS 120?F (49?C) MAXIMUM |
| |
| 2. PROVIDE SHUT OF VALVE FOR ALL DOWN FED WATER LINE |
| CAN BE ON THE BRANCH FROM MAIN LINE. PER FBC PL 606.1 |
| (5) |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |