Plan Review Notes
Plan Review Notes For Permit 19110320
Permit Number 19110320
Review Stop M
Sequence Number 1
Notes
Date Text
2020-02-07 12:53:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19110320
 11/21/19
  
 CODE IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M - FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC - FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG - FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX - FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS - FLORIDA STATUTES
 FAC - FLORID ADMINISTRATIVE CODE
 WPB - WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 1. PLEASE REFERE TO FLORIDA ADMINISTRATIVE CODE SECTION
 59A-36.025 EMERGENCY ENVIRONMENTAL CONTROL FOR ASSISTED
 LIVING FACILITIES. A DETAILED EMERGENCY ENVIRONMENTAL
 CONTROL PLAN IS REQUIRED. I HAVE COPIED ITEM (1) AND
 (1) (A) OF THE SECTION BELOW. COMPLIANCE WITH ALL ITEMS
 LISTED UNDER THE SECTION IS REQUIRED.
 (1) DETAILED EMERGENCY ENVIRONMENTAL CONTROL PLAN. EACH
 ASSISTED LIVING FACILITY SHALL PREPARE A DETAILED PLAN
 ("PLAN") TO SERVE AS A SUPPLEMENT TO ITS COMPREHENSIVE
 EMERGENCY MANAGEMENT PLAN, TO ADDRESS EMERGENCY
 ENVIRONMENTAL CONTROL IN THE EVENT OF THE LOSS OF
 PRIMARY ELECTRICAL POWER IN THAT ASSISTED LIVING
 FACILITY WHICH INCLUDES THE FOLLOWING INFORMATION:
 (A) THE ACQUISITION OF A SUFFICIENT ALTERNATE POWER
 SOURCE SUCH AS A GENERATOR(S), MAINTAINED AT THE
 ASSISTED LIVING FACILITY, TO ENSURE THAT CURRENT
 LICENSEES OF ASSISTED LIVING FACILITIES WILL BE
 EQUIPPED TO ENSURE AMBIENT AIR TEMPERATURES WILL BE
 MAINTAINED AT OR BELOW 81 DEGREES FAHRENHEIT FOR A
 MINIMUM OF NINETY-SIX (96) HOURS IN THE EVENT OF THE
 LOSS OF PRIMARY ELECTRICAL POWER.
 (2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCUATIONS FOR
 ALL ROOMS AND SPACES INVOLVED IN THE RENOVATION. SEE
 TABLE 403.3.1.1 FBC M AND PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
 (3) PROVIDE DETAILS FOR INSTALLATION OF THE WALL AC
 UNITS - SECTION 310.15 FBC M. INSTALLATIONS SHALL BE IN
 GUIDELINES FOR HURRICANE ZONE INSTALLATIONS OR SITE
 SPECIFIC ENGINEERING SHALL BE PROVIDED.
 (4) SHEET M-2: PLEASE UPDATE THE CODE REFERENCES LISTED
 IN THE HVAC NOTES TO THE CURRENT APPLICABLE EDITIONS OF
 THE FBC, NFPA, SMACNA AND ASHRAE.
 (5) THE $40,000 PROJECT VALUE ON THE PERMIT APPLICATION
 APPEARS TO BE A LOW VALUE FOR THE SCOPE OF WORK SHOWN
 ON THE PLANS. PLEASE PROVIDE COPIES OF CONTRACTS,
 ESTIMATES, INVOICES, ETC. FOR THE ENTIRE SCOPE OF WORK
 INCLUDING ARCHITECTURAL, STRUCTURAL, MEP, SITE WORK,
 DESIGN FEES, OVERHEAD AND PROFIT. PLEASE NOTE VALUE IS
 BASED ON ALL COSTS ASSOCIATED WITH THE PROJECT
 INCLUDING LABOR, MATERIALS, EQUIPMENT, FIXTURES,
 APPLIANCES, ETC.
  
 WHEN RESUBMITTING IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
 561-805-6719
 [email protected]
  