2019-11-15 14:22:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A O - THERE IS AN INDICATION OF EXISTING FIRE |
| SPRINKLER AND FIRE ALARM SYSTEMS REMAINING |
| ACTIVE....HOWEVER, THERE ARE NO INDICATIONS OF ALL NEW |
| SPRINKLER AND ALARM WORK BEING DONE UNDER SEPARATE |
| PERMITS AND SHOP DRAWINGS. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE |
| SHOP DRAWINGS AND BY CERTIFIED CONTRACTORS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| AND COMPLIANCE WITH THE ABOVE. |
| |
| |
| 2) SHEET A 4 & A 5 - THERE ARE INDICATIONS OF NEW |
| CEILING GRID SYSTEMS. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE |
| SHOP DRAWINGS AND BY CERTIFIED CONTRACTORS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| AND COMPLIANCE WITH THE ABOVE. |
| |
| |
| |
| 3) SHEETS ELECTRICAL - THE NEWLY CREATED/REMODELED |
| ROOMS REQUIRE CODE COMPLIANT FA NOTIFICATIONS. |
| |
| ANY AND ALL WORK ON THE FIRE ALARM, INCLUDING DEMO, |
| SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND BY |
| CERTIFIED CONTRACTORS. |
| |
| PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT |
| AND COMPLIANCE WITH THE ABOVE. |
| |
| |
| |
| 4) SHEETS ELECTRICAL - THE NEWLY CREATED/REMODELED |
| ROOMS REQUIRE CODE COMPLIANT SMOKE ALARMS. |
| |
| PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| ACKNOWLEDGEMENT AND COMPLIANCE WITH THE ABOVE OR |
| JUSTIFY WITH NARRATIVE AND SPECIFIC CODES REFERNECES. |
| |
| |
| |
| |
| 5) THERE IS NO INDICATION OF A LIFE SAFETY SHEETS |
| SHOWING THE NEW OCCUPANCY LOAD COUNTS OF EACH |
| FLOOR/ROOM. |
| |
| PLEASE REVIEW AND PROVIDE THE APPLICABLE LIFE SAFETY |
| DETAILS AND OCCUPANCY LOADS. |
| |
| |