Plan Review Notes
Plan Review Notes For Permit 19110257
Permit Number 19110257
Review Stop E
Sequence Number 1
Notes
Date Text
2019-12-16 09:03:18FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.201
  
 1) NOTE #8 200A DISCONNECT OR A 150A DISCONNECT???
  
 2) 250.94 INTERSYSTEM BONDING STRIP REQUIRED.
  
 3) OUTLET REQIIRED AT SERVICE RACK 210.64
  
 4) PANELS IN TRAILERS ARE ONLY RATED FOR 125A. OCP
 CANNOT BE HIGHER THAN 125A.