2019-12-17 08:14:43 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19110257 |
| ADD: 5015 ROEBUCK RD. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-494-1091 |
| E-MAIL: KCVOLBRECHT |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. DEC. 17/ 2019 |
| ACTION: DENIED |
| |
| 1) ARCHITECTURAL SHEETS 26 OF 35 AND 27 OF 35 NEITHER |
| SHOW THEY HAVE AN ELECTRONIC SIGNATURE. ARCHITECT |
| DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 PROCEDURES |
| FOR DIGITALLY SIGNING AND SEALING AND FOR |
| ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, |
| REPORTS OR OTHER DOCUMENTS. |
| |
| 2) SHEET 26 OF 35 SPECIAL NOTE 2 REQUIRES A FIRE |
| SPRINKLER SYSTEM. IN THE 2017 FBC-B SECTIONS 420.6 AND |
| 903.2.8. THERE WERE NO PLANS SUBMITTED IN THIS PACKAGE. |
| |
| 3) SHEET 26 OF 35 INDICATE WITH GENERAL NOTE D THAT THE |
| EXISTING FRAME AND FABRIC AWNING ARE TO BE DEMOLISHED. |
| IT APPEARS THEY ARE BEING REUSED AND THERE IS NOT |
| ENOUGH INFORMATION. SHEET 34 IS A STRUCTURAL SHEET FOR |
| THE LAYOUT OF THE CANOPY FOR THE FOUNDATION, WIND |
| DESIGN CRITERIA IS GIVEN ON THE STRUCTURAL SHEET 33 BUT |
| THERE IS NO SIZE OF THE STRUCTURAL MEMBERS, THERE IS A |
| NOTE STATING THAT THE CANOPY FRAME IS STEEL BUT NO |
| OTHER INFORMATION ON THE STEEL FRAMING MEMBERS NOR THE |
| REQUIRED WELD INFO TO ASSEMBLE THE USED STEEL FRAME. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| WELDED OR BOLTED CONNECTIONS |
| THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE |
| AMERICAN WELDING SOCIETY. |
| 2017 FBC-B 2204.1 WELDING |
| 2017 FBC-B 2204.2 BOLTING. |
| IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| |
| 4) ARCHITECTURAL SHEET 26 OF 28 GENERAL NOTE E STATES |
| SEE AE101 AND AE 201 FOR ADDITIONAL INFORMATION ON THE |
| EXISTING TRAILER PLANS AND ELEVATIONS. ALSO SEE AE101 |
| FOR THE PLAN OF NEW ALUMINUM WALKWAY COVER. THESE PLANS |
| WERE NOT PART OF THIS SUBMITTAL PACKAGE. 107.2.1.2. |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 5) WITHIN THIS PERMIT PACKAGE SUBMITTAL THERE WAS NO |
| ENGINEERING FOR THE TIE DOWN INFORMATION FOR THE 180 |
| MILES PER HOUR WIND DESIGN. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. 2017 FBC-B 1604.4 ANALYSIS. |
| LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR |
| CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| CHAPTER. SEE SECTION 1609 FOR WIND LOADS. |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |