2019-12-17 08:14:432017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19110257
 ADD: 5015 ROEBUCK RD.
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-494-1091
 E-MAIL: KCVOLBRECHT
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 17/ 2019
 ACTION: DENIED
  
 1) ARCHITECTURAL SHEETS 26 OF 35 AND 27 OF 35 NEITHER
 SHOW THEY HAVE AN ELECTRONIC SIGNATURE. ARCHITECT
 DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 PROCEDURES
 FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 2) SHEET 26 OF 35 SPECIAL NOTE 2 REQUIRES A FIRE
 SPRINKLER SYSTEM. IN THE 2017 FBC-B SECTIONS 420.6 AND
 903.2.8. THERE WERE NO PLANS SUBMITTED IN THIS PACKAGE.
  
 3) SHEET 26 OF 35 INDICATE WITH GENERAL NOTE D THAT THE
 EXISTING FRAME AND FABRIC AWNING ARE TO BE DEMOLISHED.
 IT APPEARS THEY ARE BEING REUSED AND THERE IS NOT
 ENOUGH INFORMATION. SHEET 34 IS A STRUCTURAL SHEET FOR
 THE LAYOUT OF THE CANOPY FOR THE FOUNDATION, WIND
 DESIGN CRITERIA IS GIVEN ON THE STRUCTURAL SHEET 33 BUT
 THERE IS NO SIZE OF THE STRUCTURAL MEMBERS, THERE IS A
 NOTE STATING THAT THE CANOPY FRAME IS STEEL BUT NO
 OTHER INFORMATION ON THE STEEL FRAMING MEMBERS NOR THE
 REQUIRED WELD INFO TO ASSEMBLE THE USED STEEL FRAME.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU.
  
 4) ARCHITECTURAL SHEET 26 OF 28 GENERAL NOTE E STATES
 SEE AE101 AND AE 201 FOR ADDITIONAL INFORMATION ON THE
 EXISTING TRAILER PLANS AND ELEVATIONS. ALSO SEE AE101
 FOR THE PLAN OF NEW ALUMINUM WALKWAY COVER. THESE PLANS
 WERE NOT PART OF THIS SUBMITTAL PACKAGE. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) WITHIN THIS PERMIT PACKAGE SUBMITTAL THERE WAS NO
 ENGINEERING FOR THE TIE DOWN INFORMATION FOR THE 180
 MILES PER HOUR WIND DESIGN. 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. 2017 FBC-B 1604.4 ANALYSIS.
 LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR
 CONNECTIONS SHALL BE DETERMINED BY METHODS OF
 STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM,
 GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH
 SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY
 STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING
 EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS
 CHAPTER. SEE SECTION 1609 FOR WIND LOADS.
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER