2019-11-18 14:26:41 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| 1) THERE ARE INCORRECT REFERNECES TO THE CURRENT FIRE |
| CODE EDITIONS. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101. |
| |
| THE BELOW LIST ARE THE MOST COMMON REFERENCED CODES: |
| |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2013 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2013 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2013 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2013 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| |
| PLEASE UPDATE YOYR RECORDS TO REFLECT THE CURRENT |
| EDITIONS OF THE FIRE CODES.REVIEW AND COMPLIANCE. |
| |
| |
| |
| 2) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR |
| FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED |
| CONTRACTORS FOR CODE COVERAGE COMPLIANCE. |
| |
| |
| 3) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE |
| SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS |
| AND SHOP DRAWINGS. |
| |
| |
| 4) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR |
| FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE |
| THROUGHOUT THE CONSTRUCTION PERIOD. |
| |
| |