2020-11-17 16:50:47 | 11/17/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, THE |
| CORRESPONDING EHD NUMBER OF THE CORRUGATED |
| STAINLESS-STEEL TUBING (IF APPLICABLE) FOR EACH PIPE |
| SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| |
| 2. SHOW THE LOCATION OF ALL REGULATORS. A LISTED |
| SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF |
| EACH REGULATOR, 2017 FBC RES. SEC. G2420.4. |
| |
| 3. YOU LISTED THE BTU'S LOAD OF EACH APPLIANCE ON THE |
| INSIDE BUT PLEASE ADD THE TOTAL BTU LOAD ON THE SYSTEM |
| FOR THE OUTSIDE GRILL, GENERATOR AND TANKLESS TO TALLY |
| A TOTAL. REFER TO THE 2017 FBC RES. SEC. G2413. |
| |
| 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| (CLOTHES DRYERS AND STOVE) 2017 FBC RES. SEC. G2407.1 |
| AND G2439.4. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017 |
| FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND |
| VENTILATION AIR SYSTEM. IF USING LOUVER FOR DRYER |
| PLEASE SHOW ON PLANS. |
| |
| 5. SUBMIT A PLAN OF A HOUSE PLAN SHOWING THE LOCATION |
| OF THE TANK-LESS WATER HEATER AND THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND-DRAWN PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| NOTE: THE TANKLESS IS NOT ON THE ISOMETRIC GAS RISER |
| BUT TWO ARE SHOWN ON THE MAIN PLAN, PLEASE CLARIFY. |
| |
| 6. SUBMIT MANUFACTURER'S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR (GRILL, GENERATOR, AND |
| TANKLESS AS SHOWN ON PLAN ) ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. |
| |
| 7. INDICATED ON THE PLAN THERE IS A GAS GRILL AND IS |
| LOCATED UNDER A ROOF. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 8. TELL ME IF THE GRILL IS LABELED FOR OUTSIDE USE AND |
| IF IT TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE |
| MANUFACTURES' RECOMMENDATION FOR A VENTILATION HOOD PER |
| THE 2017 FBC RES. SEC. G2408.1. |
| |
| 9. PLEASE SUBMIT REGULATORS MANUFACTURER'S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION PER THE 2017 FBC RES. |
| SEC. G2421.1. |
| |
| 10. IF APPLICABLE PLEASE SHOW ALL UNIONS IN FRONT OF |
| REGULATOR 1' OF EITHER SIDE PER THE 2017 FBC RES. SEC |
| G2421.2. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |