2019-12-13 13:03:20 | MECHANICAL PLAN REVIEW FAIL |
| |
| 1- RETURN AIR FOR MASTER SUITE TO SMALL PER 2017 |
| FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION SEC |
| M1602.3 BALANCED RETURN AIR. |
| |
| RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS |
| ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS |
| IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING |
| SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS |
| RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN |
| PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH |
| RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID |
| UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED |
| BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS |
| CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL |
| BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS. |
| PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING |
| SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5 |
| PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER |
| PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE. |
| |
| |
| EXCEPTIONS: |
| |
| |
| 1.TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR |
| SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN |
| AIR BALANCE. |
| |
| |
| 2.TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGHTHE-WALL TRANSFER GRILLES AND USING AN |
| UNRESTRICTED 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| |
| |
| 3.HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE |
| REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, |
| EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL |
| BE INCLUDED. |
| |
| |