Plan Review Notes
Plan Review Notes For Permit 19110025
Permit Number 19110025
Review Stop B
Sequence Number 3
Notes
Date Text
2020-01-30 10:16:12JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM
 (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561)
 805-6724
 [email protected]
  
 1ST REVIEW: FBC 2017 6TH EDITION
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF
 PROTECTIVE DEVICES OR ASSEMBLIES: PLEASE CORRECT COLUMN
 HEADING ?ANCHOR SPACING? FOR OPENINGS 2,3,4,8,9,10 AND
 12; PROVIDE INFORMATION FROM PAGE FROM PAGES 12-15 OF
 FL389-R9. EXAMPLE: MAXIMUM DESIGN PRESSURE 60, MAXIMUM
 SHUTTER SPAN 9?-0?; POURED CONCRETE; WALL HEADER
 MOUNTING TYPE A; 3? MIN. EDGE DISTANCE; ANCHOR TYPE
 TAPCON MAXIMUM ANCHOR SPACING IS 10?. MAXIMUM DESIGN
 PRESSURE 60, MAXIMUM SHUTTER SPAN 9?-0?; POURED
 CONCRETE; WALL HEADER MOUNTING TYPE D; 3? MIN. EDGE
 DISTANCE; ANCHOR TYPE TAPCON MAXIMUM ANCHOR SPACING IS
 4?.
  