Notes
Date Text
2019-11-14 14:01:081. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
 2. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. THIS PLAN DOES NOT INCLUDE ANY
 INFORMATION PERTAINING TO THE FIRE SPRINKLER SYSTEM
 WHICH IT REFERENCES, AND IN FACT SHOULD BE ATTACHED
 WITH THE MASTER PLANS AND PERMIT. ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED DURING PLAN
 RESUBMISSION.
 3.ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT. IF THE FIRE SPRINKLER DRAWINGS ARE
 CREATED BY AN ENGINEER DIFFERING FROM WHO SIGNED THE
 MASTER DRAWINGS, NOTIFICATION SHOULD BE PROVIDED IN THE
 SUBMITTAL PACKET AS TO WHICH ENGINEER IS DEFERING TO
 WHOM.
  