2019-11-14 14:01:08 | 1. PER FLORIDA ADMINISTRATIVE CODE SECTION |
| 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS |
| SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER |
| SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE |
| TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN |
| DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT |
| FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION |
| SUCH AS PRE-ENGINEERED SYSTEMS. |
| 2. A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| SUBMITTED ON THE PLANS. THIS PLAN DOES NOT INCLUDE ANY |
| INFORMATION PERTAINING TO THE FIRE SPRINKLER SYSTEM |
| WHICH IT REFERENCES, AND IN FACT SHOULD BE ATTACHED |
| WITH THE MASTER PLANS AND PERMIT. ADDITIONAL PLAN |
| REVIEW COMMENTS MAY BE GENERATED DURING PLAN |
| RESUBMISSION. |
| 3.ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| FOR A SUB-PERMIT. IF THE FIRE SPRINKLER DRAWINGS ARE |
| CREATED BY AN ENGINEER DIFFERING FROM WHO SIGNED THE |
| MASTER DRAWINGS, NOTIFICATION SHOULD BE PROVIDED IN THE |
| SUBMITTAL PACKET AS TO WHICH ENGINEER IS DEFERING TO |
| WHOM. |
| |
| S.THOMAS |
| 561-804-4728 |