2019-11-19 17:04:48 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN STATES THAT THERE IS A UPGRADED 100 AMP SERVICE |
| ON THIS STRUCTURE. IS THIS A NEW SERVICE, OR IS IT |
| BEING UPGRADED FROM AN EXISTING SERVICE? PROVIDE |
| CLARIFICATION. PROVIDE RISER DIAGRAM, SHOWING ALL |
| DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD |
| SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO |
| ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 |
| 2. IF THIS IS A NEW OR REBUILT SERVICE, PROVIDE |
| AVAILABLE SHORT CIRCUIT CALCULATION FOR SERVICE |
| INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC RE |
| E3606.3 |
| 3. SINCE ONCE SERVICE DROP IS PERMITTED PER RESIDENTIAL |
| ADDRESS, PROVIDE LOAD CALCULAITON FOR BOTH SERVICES TO |
| CONFIRM THE RATING OF THE SERVICE WIRE IS SUFFICIENT. |
| NEC 220; FBC RE E3602.2 |
| 4. ELECTRICAL NOTE NUMBER 8 IS NOT CODE COMPLANT. ALL |
| BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- |
| AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1, |
| 801.2, OR 901.2 AS APPLICABLE. |
| 5. ELECTRICAL NOTE NUMBER 19 STATES THAT LIGHTING IN |
| CLOTHES CLOSETS SHALL COMPLY WITH NEC 4/10.8/D/1, WHICH |
| DOESN?T EXIST. PROVIDE CORRECTION. NEC 410.16; FBC RE |
| E4003.12 |
| 6. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE |
| OUTLETS IN GARAGE, INCLUDING THE GARAGE DOOR OPENER. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.2 |
| 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| FROM A RECEPTACLE OUTLET. THE WALL SPACING REQUIREMENTS |
| FOR KITCHEN COUNTER SPACE STATE THAT RECEPTACLE OUTLETS |
| SHALL BE INSTALLED SO THAT NO POINT ALONG THE WALL LINE |
| IS MORE THAN 24 INCHES MEASURED HORIZONTALLY FROM A |
| RECEPTACLE OUTLET IN THAT SPACE. THE PLAN PROVIDED DOES |
| NOT MEET THIS CODE IN SOME AREAS. PROVIDE CORRECTION. |
| NEC 210.52(C)(1); FBC RE E3901 |
| 8. NOT LESS THAN ONE RECEPTACLE OUTLET, IN ADDITION TO |
| ANY PROVIDED FOR SPECIFIC EQUIPMENT, SHALL BE INSTALLED |
| IN EACH SEPARATE UNFINISHED PORTION OF A BASEMENT, IN |
| EACH ATTACHED GARAGE, AND IN EACH DETACHED GARAGE OR |
| ACCESSORY BUILDING THAT IS PROVIDED WITH ELECTRICAL |
| POWER. THE BRANCH CIRCUIT SUPPLYING THE RECEPTACLE(S) |
| IN A GARAGE SHALL NOT SUPPLY OUTLETS OUTSIDE OF THE |
| GARAGE AND NOT LESS THAN ONE RECEPTACLE OUTLET SHALL BE |
| INSTALLED FOR EACH MOTOR VEHICLE SPACE. PROVIDE |
| CORRECTION. NEC 210.52(G)(1), (2), AND (3); FBC RE |
| E3901.9 |
| 9. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR |
| SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE |
| EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12 |
| 10. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| |