2020-03-02 19:09:46 | RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #19101607 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO |
| ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR |
| IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| *****IMPORTANT: |
| ENERGY CALCULATIONS NEED TO BE SIGNED BY THE OWNER |
| BEFORE ISSUING THE PERMIT. |
| |
| |
| |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| COMMENTS TO ENERGY CALCULATIONS SUBMITTED: |
| A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION |
| (2017). |
| |
| B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING BUILDER NAME, PERMIT OFFICE AND JURISDICTION |
| NUMBER (THIS JURISDICTION IS 604700) . SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| C) ITEM #10 IS INCORRECT. PLANS CALL FOR VENTED ATTIC. |
| SEE TYPICAL WALL SECTION ON SHEET A03. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-RESIDENTIAL. |
| |
| D) PROVIDE THE NAME (NOT SIGNATURE) OF PERSON |
| PERFORMING THE ANALYSIS AND GENERATING THE REPORT AS |
| REQUIRED BY SEC. R405.4.2.1 FBC- ENERGY CONSERVATION. |
| |
| E) REVISE WINDOWS ORIENTATION. NEW WINDOW DOESN'T FACE |
| EAST. SEE PLANS AND REVISE AS REQUIRED. ALSO, REVISE |
| OVERHANG SEPARATION TO MATCH PLANS. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| F) CLARIFY WHY THE GARAGE INFORMATION IS PROVIDED IF |
| THIS IS NOT PART OF THE ADDITION. |
| AND THE CALCULATIONS SUBMITTED ARE NOT FOR THE ENTIRE |
| HOUSE. THEY ARE JUST FOR THE ADDITION ALONE. REVISE AS |
| REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |
| JULIO GOMEZ |