2020-01-31 09:44:37 | RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #19101607 |
| |
| ORIGINAL COMMENT: |
| 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.5 |
| FBC-ENERGY CONSERVATION. |
| NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| |
| A) OK |
| |
| B) OK. |
| |
| ORIGINAL COMMENT: |
| C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ENGINEER OF |
| RECORD. SEE ROOF TILE NOA SUBMITTED FOR LISTED |
| ADHESIVES. AND CLEARLY MARK PADDY SIZE AS REQUIRED BY |
| CITY POLICY FOR ALL ROOFING PERMITS. |
| |
| RESPONSE: |
| POLYSET RTA-1 ADHESIVE (NOA 18-0131.02) IS NOT LISTED |
| ON THE ROOF TILE (NOA 19-1021.02) SUBMITTED. PROVIDE |
| PRODUCT APPROVAL FOR ADHESIVE THAT IS LISTED ON THE |
| APPROVED ROOF TILE. AND, REPAST COMMENT, CLEARLY MARK |
| PADDY SIZE AS REQUIRED BY CITY POLICY FOR ALL ROOFING. |
| |
| 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) NEW ROOF TILE ADHESIVE |
| REQUIRED ON PREVIOUS ITEM . SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| ORIGINAL COMMENT. |
| 4- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.1 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN SPECIFY |
| PADDY SIZE AND PRODUCT APPROVAL IS REQUIRED. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |