2020-02-24 18:27:23RESIDENTIAL (R3) ALTERATION/ADDITION THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
 PERMIT #19101506.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 ORIGINAL COMMENT:
 1- THERE IS A NEW OPENING PROPOSED ON THE EAST WALL FOR
 THE INSTALLATION OF THE A/C WALL UNIT. OPENINGS ARE NOT
 ALLOWED ON THE WALL WHEN THE WALL IS LOCATED LESS THAN
 3 FEET FROM THE PROPERTY LINE. REVISE LOCATION OF THE
 A/C WALL UNIT. TABLE R302.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REVISED PLANS NOW SHOW TWO NEW OPENINGS ON THE NORTH
 WALL. ONE WINDOW OPENING AND ONE OPENING FOR THE
 PROPOSED A/C UNIT. SAME COMMENT APPLIES TO THIS NEW
 OPENINGS. OPENINGS ARE NOT ALLOWED ON THIS WALL EITHER
 BECAUSE IT IS LESS THAN 3 FEET FROM THE PROPERTY LINE.
 TABLE R302.1 FBC-RESIDENTIAL. SEE SURVEY AND REVISE AS
 REQUIRED.
  
 2- OK
  
 3- OK.
  
 ORIGINAL COMMENT:
 4- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE
 SPACE. PLANS WERE REVISED SHOWING A NEW DEN ROOM.
  
 A)OK.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C) CLEARLY DENOMINATE THE OTHER ROOM. WHAT IS THE
 PROPOSED USE OF THIS ROOM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NAME OF THE ROOM IS NOT SPECIFIED ON
 PLANS.
  
 D) OK.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
  
  
  
 IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 ****REVIEW IN PROGRESS.........