2020-02-24 18:27:23 | RESIDENTIAL (R3) ALTERATION/ADDITION THIRD BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #19101506. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| ORIGINAL COMMENT: |
| 1- THERE IS A NEW OPENING PROPOSED ON THE EAST WALL FOR |
| THE INSTALLATION OF THE A/C WALL UNIT. OPENINGS ARE NOT |
| ALLOWED ON THE WALL WHEN THE WALL IS LOCATED LESS THAN |
| 3 FEET FROM THE PROPERTY LINE. REVISE LOCATION OF THE |
| A/C WALL UNIT. TABLE R302.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REVISED PLANS NOW SHOW TWO NEW OPENINGS ON THE NORTH |
| WALL. ONE WINDOW OPENING AND ONE OPENING FOR THE |
| PROPOSED A/C UNIT. SAME COMMENT APPLIES TO THIS NEW |
| OPENINGS. OPENINGS ARE NOT ALLOWED ON THIS WALL EITHER |
| BECAUSE IT IS LESS THAN 3 FEET FROM THE PROPERTY LINE. |
| TABLE R302.1 FBC-RESIDENTIAL. SEE SURVEY AND REVISE AS |
| REQUIRED. |
| |
| 2- OK |
| |
| 3- OK. |
| |
| ORIGINAL COMMENT: |
| 4- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE |
| SPACE. PLANS WERE REVISED SHOWING A NEW DEN ROOM. |
| |
| A)OK. |
| |
| B) OK. |
| |
| ORIGINAL COMMENT: |
| C) CLEARLY DENOMINATE THE OTHER ROOM. WHAT IS THE |
| PROPOSED USE OF THIS ROOM. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. NAME OF THE ROOM IS NOT SPECIFIED ON |
| PLANS. |
| |
| D) OK. |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| ****REVIEW IN PROGRESS......... |