Plan Review Notes For Permit 19101506 |
Permit Number |
19101506 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2020-01-02 09:08:27 | PLUMBING COMMENTS: APPROVED W/PROVISO | | 1. WATER HEATER SHALL BE PROVIDED WITH ACCESS FOR | | INSPECTION, SERVICE, REPAIR AND REPLACEMENT WITHOUT | | REMOVAL OF PERMANENT CONSTRUCTION TO COMPLY WITH FBC PL | | 502.5 PER FBC RES P2601.1 | | 2. PROVIDE A THERMAL EXPANSION CONTROL DEVICE IN COLD | | WATER SUPPLY TO THE WATER HEATER TO COMPLY WITH FBC RES | | P2903.4 | | 3. NEW VENTS TRHROUGH ROOF SHALL NOT PENETRATE OR | | PHYSICALLY INTRUDE UPON EXISTING CONCRETE TIE BEAM OR | | BEAM BLOCK. | | 4. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | INSPECTOR'S APPROVAL | | |
|