2019-12-31 14:51:57 | RESIDENTIAL (R3) ALTERATION/ADDITION SECOND MECHANICAL |
| REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #19101506. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| ORIGINAL COMMENT: |
| 1- PROPOSED A/C WALL UNIT DOESN'T HAVE HEATING. NEED TO |
| PROVIDE UNIT WITH HEATING AS REQUIRED BY SEC. R303.10 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. AND, NOW 2 UNITS SHOWN |
| ON PLANS NEED TO HAVE HEATING. |
| |
| NEW COMMENT: |
| 2- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE |
| SPACE. IN ADDITION, PLANS WERE REVISED SHOWING A NEW |
| DEN ROOM. NEED TO REVISE THE EQUIPMENT SIZING |
| CALCULATIONS REFLECTING THE PROPOSED ROOMS. SEC. |
| R403.7.1 FBC-ENERGY CONSERVATION. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |