2019-11-14 14:41:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 1ST REVIEW |
| PLUMBING COMMENTS: DENIED |
| 1. PER WPB FBC 107.2.1, SHOW THAT THE ECOSMART 8 KW |
| ELECTRIC TANKLESS WATER HEATER INDICATED ON PLAN SHEET |
| E-1 IS CAPABLE OF PROVIDING ADEQUATE HOT WATER AS |
| REQUIRED BY FBC RES P2108.1. PROVIDE MANUFACTURER?S |
| SPECIFICATION FOR SELECTED WATER HEATER AND INDICATE |
| THE DEVICE ON PLAN SHEET P-1. |
| 2. PLAN SHEET P-1 PROVIDES A SANITARY RISER DIAGRAM AND |
| A SANITARY PLAN VIEW LAYOUT. PIPING ON THE TWO DIAGRAMS |
| DO NOT MATCH. PER WPB FBC 107.2.1, PLEASE CLARIFY. SEE |
| DETAILS BELOW. |
| A. THE BUILDING DRAIN EXITS THE BUILDING ON DIFFERENT |
| WALLS |
| B. THE RISER DIAGRAM IS CODE COMPLIANT.; THE PLAN VIEW |
| IS NOT. THE WASHER AND SINK SHALL CONNECT DOWNSTREAM OF |
| THE TUB TO COMPLY WITH FBC RES P3108. 1 WET VENTING. |
| THE WET VENT CONFIGURATIONS ON THE TWO DIAGRAMS ARE NOT |
| IN AGREEMENT. |
| 3. RE: SANITARY RISER DIAGRAM: PER FBC RES P2604.4, |
| SINK AND WASHER UNDER SLAB PIPING SHALL NOT RUN |
| PARALLEL WITH BUILDING EDGE IN FOOTER. |
| 4. WASHER VENT THROUGH THE ROOF SHALL NOT PENETRATE OR |
| PHYSICALLY INTRUDE ON THE EXISTING CONCRETE TIE BEAM OR |
| BOND BEAM. |
| 5. HORIZONTAL WASHER DRAIN FROM TRAP TO VENT SHALL |
| CONNECT TO VERTICAL ABOVE THE FLOOR TO COMPLY WITH FBC |
| RES P2601.1 AND FBC PL 802.3.3 MAXIMUM STANDPIPE |
| LENGTH. |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19101506 513 45TH ST |
| |
| |
| |
| |
| |
| |