Date Text
2019-11-14 14:41:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, SHOW THAT THE ECOSMART 8 KW
 ELECTRIC TANKLESS WATER HEATER INDICATED ON PLAN SHEET
 E-1 IS CAPABLE OF PROVIDING ADEQUATE HOT WATER AS
 REQUIRED BY FBC RES P2108.1. PROVIDE MANUFACTURER?S
 SPECIFICATION FOR SELECTED WATER HEATER AND INDICATE
 THE DEVICE ON PLAN SHEET P-1.
 2. PLAN SHEET P-1 PROVIDES A SANITARY RISER DIAGRAM AND
 A SANITARY PLAN VIEW LAYOUT. PIPING ON THE TWO DIAGRAMS
 DO NOT MATCH. PER WPB FBC 107.2.1, PLEASE CLARIFY. SEE
 DETAILS BELOW.
 A. THE BUILDING DRAIN EXITS THE BUILDING ON DIFFERENT
 WALLS
 B. THE RISER DIAGRAM IS CODE COMPLIANT.; THE PLAN VIEW
 IS NOT. THE WASHER AND SINK SHALL CONNECT DOWNSTREAM OF
 THE TUB TO COMPLY WITH FBC RES P3108. 1 WET VENTING.
 THE WET VENT CONFIGURATIONS ON THE TWO DIAGRAMS ARE NOT
 IN AGREEMENT.
 3. RE: SANITARY RISER DIAGRAM: PER FBC RES P2604.4,
 SINK AND WASHER UNDER SLAB PIPING SHALL NOT RUN
 PARALLEL WITH BUILDING EDGE IN FOOTER.
 4. WASHER VENT THROUGH THE ROOF SHALL NOT PENETRATE OR
 PHYSICALLY INTRUDE ON THE EXISTING CONCRETE TIE BEAM OR
 BOND BEAM.
 5. HORIZONTAL WASHER DRAIN FROM TRAP TO VENT SHALL
 CONNECT TO VERTICAL ABOVE THE FLOOR TO COMPLY WITH FBC
 RES P2601.1 AND FBC PL 802.3.3 MAXIMUM STANDPIPE
 LENGTH.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19101506 513 45TH ST
  
  
  
  
  
  