2019-11-25 09:53:05 | RESIDENTIAL (R3) ALTERATION/ADDITION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| PERMIT #19101506. |
| |
| NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1- THERE IS A NEW OPENING PROPOSED ON THE EAST WALL FOR |
| THE INSTALLATION OF THE A/C WALL UNIT. OPENINGS ARE NOT |
| ALLOWED ON THE WALL WHEN THE WALL IS LOCATED LESS THAN |
| 3 FEET FROM THE PROPERTY LINE. REVISE LOCATION OF THE |
| A/C WALL UNIT. TABLE R302.1 FBC-RESIDENTIAL. |
| |
| 2- PROPOSED A/C WALL UNIT DOESN'T HAVE HEATING. NEED TO |
| PROVIDE UNIT WITH HEATING AS REQUIRED BY SEC. R303.10 |
| FBC-RESIDENTIAL. |
| |
| 3- THIS IS A CHANGE OF USE FROM GARAGE TO LIVABLE |
| SPACE. TYPICALLY, GARAGES ARE BUILT WITHOUT A FLOOR |
| VAPOR BARRIER. ENGINEER OF RECORD TO PROVIDE |
| SPECIFICATIONS FOR THE CONCRETE SLAB VAPOR BARRIER AS |
| REQUIRED BY SEC. R506.2.3 FBC-RESIDENTIAL. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS. SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |