2019-11-01 06:18:15 | 11/01/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE |
| PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 2. SUBMIT BTU'S FOR THE GENERATOR TO ADD TO SYSTEM AND |
| VERIFY COMPLIANCE WITH 2017 FBC RES. SEC. G2408.1. LIST |
| THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD |
| ON THE SYSTEM. REFER TO THE 2017 FBC RES. SEC. G2413. |
| 3. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| SEC. 107.3.5.3 (12) RESIDENTIAL GAS. |
| 4. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 5. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 6. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| RES. SEC. G2413.4.1. |
| 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE |
| BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| ADDITION TO THE REQUIRED VENTILATION AIR PER THE 2017 |
| FBC RES. SEC. G2407.9.3. COMBINED COMBUSTION AIR AND |
| VENTILATION AIR SYSTEM. |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC RES. |
| SEC. G2413.2. |
| 9. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM PER THE 2017 FBC RES. SEC. G2413.3. |
| 10. PLEASE LABEL THE SHUTOFF VALVE ON GAS ISOMERIC PER |
| THE 2017 FBC RES. SEC. G2401.1.3. |
| 11. SIGNATURE OF PERSON THE DOING THE DRAWING IN |
| ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO |
| THE FBC SEC. 107.1 GENERAL. |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |