2019-11-15 19:09:17 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 212.2 |
| PLEASE SHOW THE CLEAR FLOOR SPACE. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 2. BY COMBINING THE TENET SPACE IT IS REQUIRED TO |
| PROVIDE A WATER FOUNTAIN COMPLYING WITH FBC PL TABLE |
| 402.1 AND FBC ACC 211.2, |
| |
| 3. SHT. ON THE BOTTOM OF THE SHEET IN THE CENTER OF |
| THETYP. MOUNTING SPEC SHOWS A MIRROR WITH BOTTOM OF THE |
| REFLECTIVE SURFACE AT 40 MIN THE CODE REQUIRES IT TO BE |
| 40" MAX TO THE BOTTOM. PER FBC ACC 603.3 |
| |
| 4. THE 10 GAL WATER HEATER IS TO SMALL FOR MULTIPLE |
| FIXTURE THE 10 GAL HEATERS ARE DESIGNED FOR A SINGLE |
| FIXTURE PROVIDE A LARGER HEATER OR MANUFACTURE |
| SPECIFICATIONS THAT SHOWS SIZING FOR MULTIPLE FIXTURE |
| DESIGNED TO RUN SIMULTANEOUSLY. PER WPB AMEND TO FBC |
| 107.2.1 AND FBC PL TABLE 604.4 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |