Plan Review Notes
Plan Review Notes For Permit 19101464
Permit Number 19101464
Review Stop P
Sequence Number 1
Notes
Date Text
2019-11-15 19:09:171ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BREAK ROOM SINK SHALL COMPLY WITH FBC ACC 212.2
 PLEASE SHOW THE CLEAR FLOOR SPACE. PER WPB AMEND TO FBC
 107.2.1
  
 2. BY COMBINING THE TENET SPACE IT IS REQUIRED TO
 PROVIDE A WATER FOUNTAIN COMPLYING WITH FBC PL TABLE
 402.1 AND FBC ACC 211.2,
  
 3. SHT. ON THE BOTTOM OF THE SHEET IN THE CENTER OF
 THETYP. MOUNTING SPEC SHOWS A MIRROR WITH BOTTOM OF THE
 REFLECTIVE SURFACE AT 40 MIN THE CODE REQUIRES IT TO BE
 40" MAX TO THE BOTTOM. PER FBC ACC 603.3
  
 4. THE 10 GAL WATER HEATER IS TO SMALL FOR MULTIPLE
 FIXTURE THE 10 GAL HEATERS ARE DESIGNED FOR A SINGLE
 FIXTURE PROVIDE A LARGER HEATER OR MANUFACTURE
 SPECIFICATIONS THAT SHOWS SIZING FOR MULTIPLE FIXTURE
 DESIGNED TO RUN SIMULTANEOUSLY. PER WPB AMEND TO FBC
 107.2.1 AND FBC PL TABLE 604.4
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]